 Page 17   801P5 Smart Switch
TM
 
NOTE 
PROGRAMMING MODE 
In Programming Mode, you can: 
 
Change the set points 
 
Perform field pressure calibration 
 
Program Window or Standard Mode 
 
Change the password 
 
Program display update time 
 
Program delays for both switches 
 
Scale the readout 
 
Reset the Smart-Switch
TM
 to factory defaults 
If your unit includes the 4-20 mA option, you can: 
 
Activate 4-20 mA mode 
 
Calibrate the 4-20 mA 
 
Scale the 4-20 mA output 
If your unit includes the RS232 option, you can: 
 
Set the BAUD rate 
The unit will not function as a switch while in programming 
mode. 
ENTER PROGRAMMING MODE 
To access the programming mode, press the [MENU] key (See 
Figure 7). On the initial startup, no password is required. If you 
have previously set up a password, you must enter it at this time: 
1.  When the displays show ---O, press the [UP/DOWN 
ARROW] keys to set the first digit. 
2.  Press [SELECT] to move to the next digit. 
3.  Repeat this process until display shows the correct password. 
4.  Press [STORE] to enter programming mode.