PROFIBUS-DP expansion
Proceed as follows to expand the configuration with remote I/Os 
via PROFIBUS-DP:
Adding a PROFIBUS-DP module to the XC600 controller 
X
Ensure that the default address CE000 is set on the 
module
Page 13.
X
Select Configuration_XC600 in the PLC Configuration window. 
Right-click the mouse and choose Append Subelement 
r 
XC-NET-DP-M....
This will open a window with four tabs for setting parameters 
(
Figure 51). 
X
Only change the baud rate in the Bus Parameters tab from 
9,600 kBits/s to 1500 or 12000kBit/s.
All other parameters can be left.
Adding a remote XI/ON gateway 
X
Select the element XC-NET-DP-M and right-click the mouse. 
Choose Append Subelement 
r XN-GW-PBDP-12MB....
The following window with default parameters will appear:
X
Select the Input/Output tab to configure the inputs and outputs.
X
Select the required input/output modules from the left-hand 
column and transfer them to the right column using the Select 
button.
The order of the modules in the right-hand column must match the 
configuration of the controller.
The bus refreshing module is listed in the Empty Modules group.