Amana AGK01 Installation Instruction

Page of 20
4
• Energy Management System Features
Temperature Setback  - This option can save energy dollars
for unrented or unoccupied rooms by automatically setting
back the operational temperatures. This mode of operation
is selected through the configuration routine (see Configu-
ration Settings 
section). If none of the keys on the control
pad have been pressed for an 18-hour period. The unit will
automatically go into a 3-stage setback routine; after 30
minutes, a 1 degrees setback; after 3 hours, 3 degrees, and
at 8 hours, a 7-degree setback.  NOTE: Temperature set-
back does not work with a wired remote thermostat .
Door Switch and Motion Sensor Low Voltage Terminals
(DS1, DS2, MS1, MS2) - The door switch and motion sen-
sor operate as a unit, the door switch terminals allows for
wired connection of a door sensor to the control board. The
motion sensor interprets any door movement as a signal of
occupancy. If the switch between DS1 and DS2 is closed,
the door control will interpret the room door as closed.  If
the switch between MS1 and MS2 terminals is opened (or
closed if unit is configured for normally open) the control will
interpret the action as a signal of occupancy. If thirty min-
utes pass without any door activity, Energy Management
Temperature setback activates.
Serial Port Interfaces - Two serial ports located on the con-
trol board provide easy access for two-way communications
to the control board from handheld PDA devices.  An op-
tional RF antennae can be attached for wireless communi-
cations.
Unit Features