Setpoint Profiler 
 
Video Recorder – User Manual 
 
190
 
Table 5-3   Program Profiler Prompts 
Prompt 
Range/Selections 
Definition 
DISPLAY LO LIM 
OFF or number 
Enter the lower limit for the SP Trend 
display.  Allow for the maximum and 
minimum Profiler and PV values.  
DISPLAY HI LIM 
OFF or number 
Enter the upper limit for the SP Trend 
display, allowing for the maximum and 
minimum Profiler and PV values.  
PV #1 
OFF, analog parameter, number 
Program the profiler to monitor a process 
variable.  PV #1 is trended on the SP 
Trend display.  PV #1 is compared to the 
profiler’s value to determine deviation.  
Excessive deviation between PV #1 and 
profiler value can cause a Hold 
(guaranteed soak). 
PV #2 
OFF, analog parameter, number 
This is an optional PV that can also be 
monitored and can be used to determine 
deviation from profiler value.  PV #2 is 
shown on SP Trend display’s Point/Detail 
menu. PV #2 is also trended on SP Trend 
display. 
START 
Discrete parameter, 1, 0, or OFF 
RESET/RUN 
Discrete parameter, 1, 0, or OFF 
See Reset/Run on page 185. 
HOLD 
Discrete parameter, 1, 0, or OFF 
ADVANCE 
Discrete parameter, 1, 0, or OFF 
HOT START 
Discrete parameter, 1, 0, or OFF 
FAST FORWARD 
Discrete parameter, 1, 0, or OFF 
See Fast Forward on page 187. 
SHUTDOWN 
Discrete parameter, 1, 0, or OFF 
See Shutdown on page 188. 
RAMP INCREMENT 
Discrete parameter, 1, 0, or OFF 
See External Ramp Type on page 180. 
GUARANTEED SOAK 
Discrete parameter, 1, 0, or OFF 
HOLD LEVEL/EDGE 
LEVEL or EDGE 
Select LEVEL to Hold the profiler while 
the Hold discrete is Level ON, and 
resume Run when the Hold discrete is 
Level OFF. 
Select EDGE to Hold the profiler after the 
Hold discrete changes from OFF to ON, 
and resume Run after the Start discrete 
changes from OFF to ON.