Honeywell commercial programmable t7350 Manuel D’Utilisation

Page de 44
T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT
63-4368
12
Cable Termination
The FTT network segment requires termination for proper 
data transmission performance. Use a 209541B Termination 
Module to connect two of the three termination module wires 
to the L
ON
W
ORKS®
 Bus terminals. Refer to L
ON
W
ORKS®
 Bus 
Wiring Guidelines form 74-2865 for details.
Singly Terminated Network Segment
In a singly terminated topology segment, only one termination 
is required and can be placed anywhere on the segment. 
Singly terminated segments use the yellow and brown wires. 
If the network topology requires a singly terminated 
termination module at a T7350H, connect the singly 
terminated module wiring on the appropriate terminals as 
shown in Fig. 6
.
Fig. 6. Singly terminated LonWorks® bus termination 
module.
Doubly Terminated Daisy-Chain Network Segment
In a doubly terminated daisy-chained topology segment, two 
terminations are required, one at each end of the topology 
segment. Doubly terminated segments use the orange and 
brown wires. If the network topology requires a doubly 
terminated module at a T7350H (T7350H is the first or last 
device on the network cable) connect the termination module 
wiring on the appropriate terminals as shown in Fig. 7. For 
additional wiring information, refer to the E-Bus Wiring 
Guidelines, form 74-2865, and the Excel 10 FTT Termination 
Module Installation Instructions, form 95-7554.
Fig. 7. Doubly terminated L
ON
W
ORKS®
 bus termination 
modules.
CAUTION
Electrical Shock or Equipment Damage Hazard. 
Can shock individuals or short equipment 
circuitry. 
Disconnect power supply before installation.
IMPORTANT
All wiring must agree with applicable codes, ordi-
nances and regulations.
1.  Loosen subbase terminal screws and connect system 
wires.
NOTE: Maximum (and recommended) wire size is 18-
gauge. Do not use wire smaller than 22-gauge. Fol-
low equipment manufacturer wiring instructions 
when available. Refer to the Wiring Diagram section 
for typical hookups. A letter code is located near 
each terminal for identification. Refer to the Specifi-
cations section, Tables 8 and 9 for terminal designa-
tions.
2.  Securely tighten each terminal screw.
3.  Push excess wire back into the hole in the wall.
4.  Plug the hole with nonflammable insulation to prevent 
drafts from affecting the thermostat.
Wiring Details
L
ON
W
ORKS®
 network cable should be wired separately from 
the power and I/O wires when installing T7350H models. If 
this is not possible, use a minimum of 4 in. (102 mm) 
separation between split ferrite cores (Fair-Rite 0443164151, 
www.fair-rite.com) to ensure compliance with Class B limits 
(does not apply to Class A limits). See Fig. to apply ferrite 
cores to L
ON
W
ORKS®
 Bus input and output.
Step 4. Prepare Wiring Diagrams
show T7350 terminal arrangements and 
provide detailed wiring diagrams. Reference these diagrams 
to prepare the site-specific job drawings.
Fig. 8. Ferrite core wires from T7350H to L
ON
W
ORKS®
 
inputs and outputs.
ORANGE
BROWN
YELLOW
PART NO. 209541B
TERMINATION MODULE
M22494
RC
AUX
X
SUBBASE
W1
G
Y1
W3/Y4 Y3
W2
Y2
AUX
RH
T5
T6
T7
T4
T3
M
OS
OS
AS
AS
M
HC
HP
HS
EB
EB
YELLOW
BROWN
ORANGE
PART NO. 209541B
TERMINATION MODULE
M22495
RC
AUX
X
SUBBASE
W1
G
Y1
W3/Y4 Y3
W2
Y2
AUX
RH
T5
T6
T7
T4
T3
M
OS
OS
AS
AS
M
HC
HP
HS
EB
EB
M22496 
WIRES TO T7300H
COMMUNICATING SUBBASE
WIRES TO T7300H
COMMUNICATING SUBBASE
WIRES TO ALL
INPUTS AND 
OUTPUTS
WIRES TO ALL
INPUTS AND 
OUTPUTS
1.
2.