Honeywell commercial programmable t7350 Manuel D’Utilisation

Page de 44
T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT
63-4368
10
value will be used in the T7350H as the primary controlled 
variable. The local space temperature sensor of the 
T7350H is ignored until the network sensor fails.
• Space Humidity Sharing: 
If a valid humidity value is received at the T7350H Space 
Humidity network variable input, that value will be used in 
the T7350H as the humidity control variable. The local 
space humidity sensor of the T7350H is ignored until the 
network sensor fails. 
• Current Setpoint Sharing: 
If a valid setpoint value is received at T7350H nviSetpoint, 
that value will be used by the T7350H as the center 
setpoint. The heat and cool setpoints are then calculated 
from this value and are used in the T7350H as the 
occupied setpoints. During unoccupied periods, 
nviSetpoint is ignored. 
• Occupancy Sensor Sharing: 
If a valid value is received at the T7350H occupancy 
sensor network variable input, that value will be used in the 
T7350H as the occupancy sensor. The local T7350H 
occupancy sensor is ignored until the network sensor fails. 
NOTE: The occupancy or motion sensor is active whenever 
the device is scheduled “Occupied” and a remote or
 
network occupancy sensor is configured.
The T7350H effective occupancy is determined in Table 6.
Table 6. T7350H Effective Occupancy.
• Occupancy Bypass: 
Any internal or external scheduled unoccupied state in the 
T7350H is overridden by a network occupancy bypass 
command. Bypass is a method to command unoccupied 
override over the network from another controller (typically 
a T7350H or XL10). The source controller manages the 
bypass timing. 
• Manual occupancy: 
Provides a method to command the occupancy state from 
a network workstation. Effective occupancy override works 
on a “last in wins” basis. That is, the last occupancy 
override command received from any source determines 
the override state. The workstation can command 
occupied, unoccupied, standby, bypass, or not active (null). 
There are several ways to return the device to normal 
schedule operation. 
1. Power failure reset at the T7350H.
2. Workstation issues a “not active” (null) network com-
mand to T7350H.nviOccManCmd.
3. User activates “Temporary Occupied” button on the 
local keyboard. This can be followed by a “Run Sched-
ule” local command.
4. If manual occupancy is commanded to bypass and the 
bypass timer times out.
APPLICATION STEPS
Overview
The application steps shown in Table
are guidelines for 
configuring the T7350H in a L
ON
W
ORKS®
 Bus network and 
explain the network role of the T7350H.
Table 7. Application Steps.
 Source
 Destination
T7350H.nvoSpaceTemp 
or XL10.nvoSpaceTemp
T7350H.nviSpaceTemp
 Source
 Destination
T7350H.nvoSpaceRH
T7350H.nviSpaceRH 
or XL15c.nviRARH
 Source
 Destination
T7350H.nvoEffectSetpt
or XL10.nvoEffectSetpt
T7350H.nviSetpoint
 Source
 Destination
T7350H.nvoOccSensor 
or XL10.nvoSensorOcc
NetworkSensor
T7350H.nviOccSensor
Schedule
Occupancy
Occupancy/Motion 
Sensor Contact
Effective 
Occupancy
Occupied
Open
Standby
Occupied
Closed
Occupied
Standby
NA
Standby
Unoccupied
NA
Unoccupied
 Source
 Destination
T7350H.nvoBypass 
or
XL10.nvoBypass
XL15a.nvoBypass[i]
XL15c.nvoBypass[i]
T7350H.nviBypass
 Source
 Destination
Workstation
Command Display
XL15b
T7350H.nviOccManCmd
 Step
 Description
1
Plan the system.
2
Determine required network devices.
3
Lay out communications and power wiring.
4
Prepare wiring diagrams.
5
Order equipment.
6
Configure T7350.
7
Troubleshooting.