Honeywell commercial programmable t7350 Manuel D’Utilisation

Page de 44
T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT
63-4368
8
L
ON
M
ARK®
 Functional Profile
Fig. 3. T7350H L
ON
M
ARK®
 Space Comfort Controller Rooftop Object (8504) with Node Object.
nv28
nv26
nvoSpaceTemp
SNVT_ temp_p
nv27 nvoUnitStatus
SNVT_hvac_status
nvoEffectSetpt
SNVT_temp_p
Hardware Output
Hardware Output
Hardware Input
Hardware Input
SCC-Rooftop
Object Number 8504.
Mandatory
 Network
Variables
Manufacturer
Defined
Section
Optional
Network
Variables
Configuration Properties
nv45
nvoOutdoorTemp
SNVT_temp_p
nv29
nvoEffectOccup
SNVT_occupancy
nv30
nvoHeatCool
SNVT_hvac_mode
nv34
nvoDischAirTemp
SNVT_temp_p
nv37
nvoTerminalLoad
SNVT_lev_percent
nv43
nvoSpaceRH
SNVT_lev_percent
nv7
nviOccSensor
SNVT_occupancy
nv2
nviSetpoint
SNVT_ temp_p
nv6
nviOccManCmd
SNVT_occupancy
nv5
nviOccSchedule
SNVT_tod_event
nviSpaceTemp
SNVT_temp_p
nv1
nv8
nviApplicMode
SNVT_hvacMode
nv19 nviOutdoorTemp
SNVT_Temp_p
nv20 nviSpaceRH
SNVT_lev_percent
nv43
nvoBypass
SNVT_switch
nv44
nvoOccSchedule
SNVT_tod_event
nv45
nvoOccSensor
SNVT_occupancy
nv46
nvoData1
UNVT_data1
nv47
nvoData2
UNVT_data2
nv30
nviBypass
SNVT_switch
nv31
nviFanAuto
SNVT_switch
nv32
nviManValue
UNVT_manValue
nv34
nviDlcShed
UNVT_dlcShed
M22431
SNVT_time_sec
SNVT_time_sec
SNVT_temp_setpt
SNVT_time_min
UCPTconfig
UCPTconfigPts
UCPTdaylightSav
UCPTschedule0
UCPTschedule1
UCPTschedule2
UCPTschedule3
UCPTschedule4
UCPTschedule5
UCPTschedule6
UCPTschedule7
UCPTholSched
(mandatory)
(optional)
(mandatory)
(optional)
(manf specific)
(manf specific)
(manf specific)
(manf specific)
(manf specific)
(manf specific)
(manf specific)
(manf specific)
(manf specific)
(manf specific)
(manf specific)
(manf specific)
nc1 - nciSndHrtBt
nc4 - nciRevHrtBt
nc2 - nciSetpoints
nc6 - nciBypassTime
         nciConfig
         nciConfigPts
         nciDayLghtSav
         nciDaySchedule0
         nciDaySchedule1
         nciDaySchedule2
         nciDaySchedule3
         nciDaySchedule4
         nciDaySchedule5
         nciDaySchedule6
         nciDaySchedule7
         nciHolSched
nv6
nv2
nvoStatus
SNVT_ obj_status
nvoFileStat
SNVT_file_status
Node
Object
Mandatory
 Network
Variables
Manufacturer
Defined
Section
Optional
Network
Variables
Configuration Properties
nv3
nviTimeSet
SNVT_ time_stamp
nv7
nviFilePos
SNVT_file_pos
nv5
nviFileReq
SNVT_file_req
nviRequest
SNVT_obj_request
nv1
nv11
nroT7350Ver
UNVT_version
nv12
nroPgmVer
UNVT_pgmId
nv13
nvoPgm
UNVT_pgmOut
nv14
nvoTime
SNVT_time_stamp
nv15
nvoAlarmH
UNVT_alarm
nv16
nvoAlarmStatus
UNVT_alarmStatus
nv17
nvoAlarmLog
UNVT_alarmLog
nv18
nvoError
UNVT_error
nv9
nviInUse
UNVT_inUse
nv10
nviPgm
UNVT_pgmIn
UCPTdevName
UCPTapplVer
(manf specific)
(manf specific)
nc1 - nciDeviceName
nc2 - nciApplVer