T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT
9
63-4368
NETWORK CONFIGURATIONS
The T7350H can be configured to perform a variety of 
activities in which data is sent to and/or received from other 
nodes on the L
ON
W
ORKS®
 network. Information that can be 
shared with other network devices includes:
— Current year, month, day, hour, minute, second.
— System mode (HEAT, COOL, AUTO, OFF, EM HEAT).
— Current fan setting (ON, AUTO).
— Space temperature.
— Space relative humidity.
— Discharge air temperature.
— Outdoor air temperature.
— Occupancy sensor status.
— Terminal load.
— Current setpoint.
— Occupied/Unoccupied schedule commands.
— Current occupancy status.
— Occupancy schedule including current occupancy state, 
next state and time in minutes until next scheduled 
change of occupancy state.
— Relay status (heat/cool stages and fan).
— Alarm status.
— Alarm log including the last five alarms.
— Device Error status.
— Bypass state (multiple XL10 devices follow the bypass 
operation of a master device).
A network configuration tool is used to configure the T7350H 
Thermostats and other nodes with which the T7350H 
interacts. The following is a brief description of the 
configurable features that can be commanded over the 
network:
• Time  Master: 
When a T7350H is designated as the network time master, 
the current time of day and date is synchronized across the 
network every minute. The L
ON
S
PEC
™ T7350H General 
Screen can be used to configure a T7350H as the Network 
Time Master. Whenever the time of day or date of the time 
master is changed, it automatically adjusts all the other 
network devices (T7350H, Q7300 & XL15A) bound to the 
time master. When a T7350H is controlled by a time 
master, the local day light saving schedule is disabled. The 
Day Light Saving option on all time master recipients 
should be disabled. This prevents erroneous time changes 
(local daylight savings switchover) during temporary 
network outages. 
• Time Schedule: 
The occupancy schedule used by a T7350H may reside 
locally in that device or remotely in another schedule 
device (T7350H, XL15a, XL15b or T7300/Q7300). Local 
schedules can be created and modified using the T7350H 
keypad, a direct connected PDA, a network connected 
configuration tool (L
ON
S
PEC
™) or Command Display. 
External schedules can also be modified using the keypad 
of the master schedule device, or with a network 
connected configuration tool or Workstation. When a 
T7350H receives scheduling information over the network, 
the user is not prevented from making local schedule 
changes at the recipient thermostat. Local schedule 
changes (at a recipient device) have no effect on the 
scheduling commands received from the master device. 
When a T7350H is designated as a master schedule 
device, it sends its schedule information (current state, 
next state, time until next change of state) to the 
appropriate T7350H(s) which, in turn, overrides any 
existing internal time schedule. The T7350H Thermostat 
can provide master scheduling information to multiple 
Excel 10 devices. One T7350H shares the schedule 
information (current state, next state, time until next 
change of state) with the designated Excel 10 devices. 
• System Mode Settings: 
System mode settings (HEAT, COOL, AUTO, OFF, EM 
HEAT) can be commanded by a remote T7350H or other 
compatible XL10 device. A one to many network binding 
can be used to command multiple devices from a single 
unit. In addition, a network connected Workstation can be 
used to change the System Mode.
• Fan Settings: 
Fan settings (ON, AUTO) can be changed from a network 
connected Workstation. 
• Outdoor Air Temperature Sharing: 
If a valid outdoor air temperature value is received at the 
T7350H OAT network variable input, that value will be used 
in the T7350H. The local OAT sensor of the T7350H is 
ignored until the network sensor fails.
• Discharge Air Temperature Sharing: 
The discharge air temperature value can be shared with 
other devices on the network. Note that the T7350H does 
not accept a network discharge air temperature input.
• Space Temperature Sharing: 
If a valid space temperature value is received at the 
T7350H Space Temperature network variable input, that 
 Source
 Destination
T7350H.nvoTime 
or
XL15a.nvoTimeOut
Q7300.nvoTime
T7350H.nviTimeSet 
or
XL15a.nviTimeIn
Q7300.nviTime
 Source
 Destination
T7350H.nvoOccSchedule 
or
XL15a.nvoTodEventCmd[i]
Q7300.nvoOccSchedulei
T7350H.nviOccSchedule 
or
XL10.nviTodEvent
XL15c.nviTodEventIn[i]
 Command Source
Command Destination
T7350H.nvoHeatCool 
or Workstation
T7350H.nviApplicMode
 Source
 Destination
Workstation 
or Network Tool
T7350H.nviFanAuto
 Source
 Destination
T7350H.nviOutdoorTemp 
or
XL10.nvoOdTemp
XL15c.nvoOdTemp
T7350H.nvoOutdoorTemp 
or
XL10.nviOdTemp
XL15c.nviOdTemp
 Source
 Destination
T7350H.nvoDischAirTemp
XL15c.nviDATemp