APPENDIX B
* Before the SCR can be reset, the system must be checked and repaired by a licensed contractor. To reset the SCR, 
insert a rigid, small-diameter object (e.g. paperclip) into the smallest hole in the face of the SCR, next to the green 
connector block. This, too, should be performed by an HVAC contractor.
Table 4. Safety Control Relay (SCR) Operation and Troubleshooting Guide.
Condition
Cause
Action Required
SCR LED shows rapid series of red, 
green, and yellow lights, followed by 
no LED display.
Condition Normal. SCR processor is 
powering up and checking internal 
operation.
No action required.
Humidifier won't operate. No SCR 
LED display.
Problem! SCR circuit is not closing or 
humidistat is not calling for humidity. 
Check SCR power; check humidistat 
operation. If humidity is about 45% or 
outdoor temperature is above 50°F, 
the humidifier won't operate unless the 
humidistat is set to Test mode. 
Humidifier operates. SCR LED shows 
continuous yellow.
Condition Normal. This is a test phase. 
SCR will wait 30 minutes to detect 
furnace blower operation. If the 
furnace blower is detected, the system 
will function properly. 
No action required.
Humidifier won't operate. SCR LED 
shows continuous red.
Problem! During the 30 minute test 
phase, the SCR failed to detect the 
furnace blower and turned the 
humidifier off. 
Turn the humidistat off, then on again, 
to reset the system. Although unlikely 
to occur, this failure/reset process can 
occur twice before further action is 
necessary.
Humidifier operates. SCR LED shows 
continuous green.
Condition Normal. All systems 
(furnace, humidistat, humidifier and 
SCR) are operating properly.
No action required.
Humidifier won't operate. SCR LED 
shows flashing red. 
Problem! The SCR failed to detect the 
furnace blower for the third time and, 
as a safety precaution, has locked out 
the humidifier. This is an indication 
that some aspect of the system 
(furnace, humidistat, humidifier or 
SCR) has malfunctioned.
Contact your HVAC contractor ASAP 
to check out and repair the system.*