HE420A STEAM POWER HUMIDIFIER
7
69-1108—2
APPENDIX A
Table 3. Compensating Humidistat Troubleshooting Guide. 
PROBLEM
SOLUTION
NOTES
Humidifier does not 
operate in “Test” 
mode.
• Confirm the outdoor temperature sensor is 
connected to the correct terminals on the 
humidistat. (For manual operation, ensure the 
jumper pins are positioned correctly.)
• Check wiring diagram (Figure 1) for correct 
installation.
• Check the voltage at the humidistat “24 VAC” 
terminals. (Should be 22-30 VAC.)
• Ensure the control knob has not been left in the 
“Test” position.
Humidifier only 
operates in “Test” 
mode.
• Check the resistance of the sensor by removing 
the leads from the humidistat terminals and 
measuring the resistance across the wires with 
an ohmmeter. Compare the reading to the 
temperature/resistance chart (right).
• For automatic applications, make sure the 
outdoor temperature sensor is mounted 
completely outside the house (i.e. not recessed 
into the hole) on the North, Northeast or 
Northwest side, away from direct sunlight. And is 
mounted at least 3 feet away from all exhaust 
vents.
• If the outdoor temperature sensor is mounted in 
the fresh air intake duct, make sure the probe is 
no further than 30 inches from an outside wall.
Temp/Resistance Chart
100°F
6000 ohms
38°C
90°F
7500 ohms
32°C
80°F
9500 ohms
27°C
70°F
11,500 ohms
21°C
60°F
14,000 ohms
16°C
50°F
18,000 ohms
10°C
40°F
23,000 ohms
4°C
30°F
28,500 ohms
-1°C
20°F
37,000 ohms
-7°C
10°F
46,500 ohms
-12°C
0°F
61,500 ohms
-18°C
-10°F
78,500 ohms
-23°C
-20°F
105,500 ohms
-29°C
-30°F
135,000 ohms
-34°C
Notes:
In automatic applications, if the outdoor 
temperature is greater than +50°F (+10°C) 
or less than -32°F (-35.6°C), the 
compensating humidistat will not operate 
(except in “Test” mode).
In both automatic and manual applications, 
if the relative humidity in the home is 
higher than the knob setting, the 
humidistat will not operate. Similarly, the 
humidistat will not operate if the indoor RH 
exceeds 45%.
Humidifier operates 
constantly.
• Check the humidistat setting. If the RH in the 
home is less than the knob setting, the humidifier 
will operate until the humidity level is higher than 
the knob setting. 
• In “Test” mode, verify that the humidifier will shut 
off after approximately one minute.
• Check the resistance of the sensor.
• See previous Problem/Solution, regarding 
outdoor temperature sensor mounting locations.
• Turn the humidistat “OFF” and observe whether 
the humidifier turns off. If operation continues, 
check Figure 1 wiring diagram. Remove the 
wires from the humidistat's “OUT” terminals. If 
humidifier continues to operate, check the 
humidifier.
Humidifier or 
compensating 
humidistat “chatters” 
or clicks on and off 
rapidly.
• Use a voltmeter to check for steady 22-30 VAC.
• Make sure the outdoor temperature sensor 
wiring does not run alongside the wires carrying 
high voltage (120 VAC or higher).
Furnace or heat 
pump blower system 
runs continuously; 
condensation is 
building up in 
ductwork.
• It may be necessary to make a setting change on 
the furnace or heat pump board to prevent the 
blower from shifting down to lowest idling speed.
• Consult the furnace/heat pump operating manual 
or contact the manufacturer for procedures to 
prevent low air flow.