SE-4200/4400 WATER FILTRATION SYSTEM
8
P/N 1010852 Rev. C 04/06
2”  
minimum
2”  
minimum
Floor 
Drain
Secure 
End
Drain Line from 
System
Drain Line from 
System
Secure 
End
 
Drain
Standpipe
INSTALLATION (continued)
Locating and Mounting the system
Consider these points before mounting the system:
•  Note the location of the water supply, drain, and 
an appropriate electrical outlet when choosing a 
mounting location.  
•  Remember to allow for access to the Control Box.  
•  Do not mount the system above any electrical 
equipment or items that may be damaged if they 
get wet.  
•  Install the system in a location that will allow for 
future service access.  
•  Mount the system on a wall using appropriate 
mounting hardware.  
•  Remember to consider the operating weight of 
the system when choosing mounting hardware.  
Depending on the type of wall on which the system 
is mounted, wall reinforcement may be necessary.
INLET WATER PLUMBING
It is recommended that the inlet water plumbing line 
be 3/4” NPT or larger.  A shutoff valve (not supplied) 
should be installed in the line leading to the system.  
The valve should be mounted close to the system inlet, 
and sized properly for the inlet plumbing line.  The sys-
tem should only be connected to the cold water line.
PERMEATE LINE PLUMBING
To ensure the highest quality and safest water, it is 
recommended that a check valve (to prevent backflow) 
be installed in the water line after the permeate connec-
tion.  This will help prevent possible contamination of 
the filter system due to other equipment downstream.  
The check valve (not supplied) should be mounted 
close to the system outlet, and sized properly for the 
plumbing line.  Check with local codes for the proper 
specification.
DRAIN LINE PLUMBING
The drain line is used to flush away the particle buildup 
when cleaning the filter.  The drain line must be able 
to support the flow rate when the system flushes.  The 
flow rate from the flush depends on the inlet water pres-
sure, inlet pipe size, and system selected.  It is recom-
mended that the drain line be as large as, or larger 
than, the inlet plumbing line.  The drain line should be 
as short as possible, sloping downward without kinks 
or loops.  Be sure that the drain used is not blocked or 
restricted.  
The filter system must be protected from possible back 
contamination by the installation of an air gap between 
the drain connection of the system and the drain 
(Figure 1).  This gap in the line, with no physical contact 
between the system and sewer, prevents contamination 
of the system in the event of a backed-up sewer.  
NOTE: Make sure that the end of the drain line is 
positioned and secured at least 2 inches above 
the drain so that the water flow is directed into the 
drain, without splashing (Figure 1).
Figure 1. Proper Draining