Breckwell W3000 사용자 설명서

다운로드
페이지 13
 
 
 
 
 
VENTING 
 
FREESTANDING 
 
The W3000FS is approved for use with double wall connector and 
the same manufacture’s chimney systems as follows: 
 
Simpson Dura-Vent Model DVL 
Selkirk Metalbestos DS 
Security Chimneys Model DL 
 
1. 
Install the chimney by following the manufacture’s instructions. 
YOUR CHIMNEY MUST COMPLY WITH LOCAL BUILDING 
AND FIRE CODES. 
2. 
Install the first piece of pipe, crimped end down, into the flue 
collar on the stove ensuring an airtight connection. Continue 
stacking pipe in this manner until within reach of chimney. Use 
only an air tight slip joint to make the connection to the 
chimney. 
 
All horizontal runs of pipe should be as short as possible and are 
required by NFPA No. 211 to have an upward pitch or rise in the 
same direction the smoke travels of no less than ¼” to the linear 
foot. The connector pipe must meet minimum clearances in any 
direction to walls or other combustible materials. It must attach to a 
listed metal  chimney at least 6” in diameter with a minimum 
thickness of 24 gauge, or to a masonry chimney with a flue passage 
of at least 48 square inches. 
 
It is required that a chimney connector pipe not extend further than 
the inner wall of the flue when it is connected to a masonry chimney, 
and that it either be cemented to the masonry or be installed without 
cement in a thimble connected to the masonry wall. When the 
connector is inserted in a thimble, the joint must be tight enough so 
that it will not be dislodged in normal use. Install the connector at no 
less than the minimum clearances from the ceiling when using a 90-
degree elbow to pass through combustible constructions. 
 
Chimney connector pipes should never pass through a floor, ceiling, 
firewall, and partition or combustion construction of any type unless 
certain precautions are taken. The best method is to use a listed 
thimble and a listed insulated chimney in accordance with the 
manufacturer’s directions. NFPA No. 211 also gives some approved 
methods for passing a flue pipe through combustible constructions. 
INSERT 
 
INSTALLATION PROCEDURE FOR MASONRY CHIMNEY 
 
NOTE: Although not required, a full length stainless steel liner 
(UL1770) is recommended for optimum safety and 
performance. 
 
1. 
Read entire installation instructions and complete and return 
the warranty card. 
2. 
Check all required clearances as specified in figure 3. 
3. 
Open or remove the existing fireplace damper. 
4. 
Locate the leveling nuts on each side of the outer chamber of 
the stove at the lower rear corners. Install the supplied carriage 
bolts with the head down, through each nut from the bottom 
sides and not extending below the stove bottom. 
5. 
Position the stove on the hearth and in far enough so that the 
flue opening and the damper are aligned. The stove may need 
to be offset to one side to allow enough room to connect the 
pipe. 
6. 
When the W3000I is installed in a Masonry chimney the 
stainless steel liner must directly connect at least up to the tile 
liner. 
7. 
Center and push the stove in flush with the fireplace face. 
Adjust the leveling bolts until the stove is level. 
8. 
Install the flashings and push the stove up snug against the 
face of the fireplace. 
 
REQUIREMENTS FOR FACTORY-BUILT ZERO 
CLEARANCE FIREPLACE 
 
NOTE: When the W3000I is installed in a zero clearance factory-
built fireplace the liner must be 6 inch stainless steel (UL1770) 
and be lined to the chimney top. 
 
1. 
The W3000I must only be installed in a zero clearance factory-
built fireplace that is structurally sound. Fireboxes or chimneys 
that have flaws, burn-outs, or warpage must be replaced or 
repaired prior to installation. Check with your fireplace 
manufacturer if any problems exist. 
2. 
All convection vents and louvers must be left unmodified and 
unobstructed. 
3. 
The W3000I can be installed in factory-built zero clearance 
fireplaces with minimum cavity dimensions of 36 inches in 
width, 22 inches in height, and 14 inches in depth. 
4. 
Modifications allowed to the factory-built fireplaces are as 
follows: 
  Removal of the damper. 
  Removal of the smoke shelf on the baffle. 
  Removal of the ember catches. 
  Removal of the viewing screen/curtain. 
  Removal of the side and rear bricks. 
  Removal of the fire grate. 
  Removal of the doors. 
 
DO NOT CONNECT THIS UNIT TO A CHIMNEY FLUE SERVING 
ANOTHER APPLIANCE. 
 
INSTALL VENT AT CLEARANCES SPECIFIED BY THE VENT 
MANUFACTURER.
 
 
 
 
 
 
 
 
 
 
 
INSTALLATION 
FIGURE 3