Chateau™ Decorative Gas Appliance
20009543
Always check for gas leaks with a mild 
soap and water solution applied with a 
brush no larger than 1” (25mm). Never ap-
ply soap and water solution with a spray 
bottle. Do not use an open flame for leak 
testing.
The fireplace valve must not be subjected 
to any test pressures exceeding   1/2 psi. 
Isolate or disconnect this or any other gas 
appliance control from the gas line when 
pressure testing.
The gas control is equipped with a captured screw type 
pressure test point, therefore it is not necessary to pro-
vide a 1/8” test point up stream of the control.
When using copper, use only approved fittings. Always 
provide a union
 when using black iron pipe so the gas 
line can be easily disconnected for burner servicing. A 
union may not be behind a wall. (Fig. 8) See the gas 
specifications for pressure details and ratings.
The fireplace, when installed, must be elec-
trically connected and grounded in accord-
ance with local codes or, in the absence 
of local codes, with the current CSA C22.1 
Canadian Electrical Code or the national 
electrical code  ANSI/NFPA No. 70 in the 
USA.
It is strongly suggested that the wiring of 
the Electrical Junction Box be carried out 
by a licensed electrician. The box should 
be near the valve box assembly to plug the 
cord into.
Ensure the power to the supply line has 
been disconnected before commencing 
this procedure.
Electrical Junction Box (E Units Only)
Do not wire the remote ON/OFF wall switch 
for this gas appliance into a 120V power 
supply.
The unit is equipped with an ON/OFF rocker switch at 
the valve box assembly. If a wall switch is desired, fol-
low these instructions.
1.  The valve box is equipped with two knockouts at 
the top right and left corners. The right knockout is 
designed to run the wall switch wires to the valve. 
Use Romex connectors when running wires through 
the valve box where the knockouts are located.
2.  Attach the wire to the ON/OFF switch and install the 
switch into the receptacle box.
3.  Connect the other end of the wire to the gas control 
valve. (Fig. 9) 
Remote ON/OFF Switch
  
HI 
   
  
  
   
   LO 
      
       
  
ON
    
  
  
   
   OFF 
  
E
A
  PIL
OT
 
THTP
TP
TH
������
���������
�������������
������
����
Fig. 9  Remote switch wiring diagram for R models.
Remote ON/OFF 
Switch
Gas Control Valve
FP1366
This appliance may be fitted with a Honeywell ignition 
module. The unit is shipped from the manufacturer with 
an ON/OFF switch. The ON/OFF switch is located in 
the valve box assembly. If desired a wall switch may be 
used.  
Installation of the remote ON/OFF switch on electronic 
ignition units: 
1.  The valve box is equipped with two knockouts at the 
top right and left corners. The right knockout is de-
signed to run the wall switch wires to the valve. The 
left knockout is designed for wiring the electronic 
unit (E model) to 120v with proper grounding. Use 
Romex connectors when running wires through the 
valve box where the knockouts are located.
2.  Attach the wire to the ON/OFF switch and install the 
switch into the receptacle box. (Fig. 10)
3.  Connect the White wire from the wall switch to the 
Black wire from the transformer, using an approved 
wire nut or terminal. Connect the Black wire from the 
wall switch to the Black wire running from the #6 po-
sition of the ignition module, also using an approved 
wire nut or terminal.
Electronic Gas Control Valve