INSTALLATION
FLUEING ARRANGEMENTS - HORIZONTAL TERMINATIONS
SIMPSON DURA-VENT DIRECT VENT GS SYSTEM and
REGENCY
®
 DIRECT VENT SYSTEM (FLEX)
(LPG & NG)
The diagram shows all allowable combinations of vertical runs with horizontal terminations, using one 90
o
 elbow (two  45
elbows equal
one 90
o
 elbow).
Note: Must 
use 
optional 
fl ue adapter (Part # 510-994) when using Simpson Dura-Vent pipe.
Simpson Dura-Vent
4" (102mm) inner diameter
6-5/8" (168mm) outer diameter
Regency
®
 Flex Vent
4" (102mm) inner diameter
6-7/8" (175mm) outer diameter
•   Maintain clearances to combustibles as listed in section "Clearances."
•   Horizontal fl ue must be supported every 3 feet (0.9 meters).
•   Firestops are required at each fl oor level and whenever passing through a wall.
A fl ue guard should be used whenever 
the termination is lower than the 
specifi ed minimum or as per local 
codes.
Note: Regency
®
 Co Axial Flue System 
(Flex) is only approved for 
horizontal terminations.