Regency Wraps P36-LPG4 Manual Do Utilizador

Página de 44
Regency
®
 P36-4 Gas Log Fireplace
15
INSTALLATION
FLUEING ARRANGEMENTS - VERTICAL TERMINATIONS
SIMPSON DURA-VENT CO AXIAL FLUE GS SYSTEM
 
(LPG & NG)
The P36 is approved for a  23 ft. (7.0m)  vertical,  with a maximum 12 ft. (3.7m) horizontal offset 
using two 90
o
 elbows (two  45
elbows equal one 90
o
 elbow) with Simpson Dura-Vent Co Axial 
Flue GS fl ue systems for LPG and NG, as per diagram 1.
The P36 is approved for a  37 ft. (11.3m) straight vertical, including a 20" (0.5m) horizontal offset 
using two 90
o
 elbow (two  45
elbows equal one 90
o
 elbow)  with Simpson Dura-Vent Co Axial 
Flue GS fl ue systems for LPG and NG, as per the diagram 2.
•   Flue must be supported at offsets
•   Maintain clearances to combustibles as listed in section "Clearances."
Note: Must 
use 
optional 
fl ue adapter when using Simpson Dura-Vent pipe
  
(Part 
510-994).
Note: Regency
®
 Co Axial Flue System (Flex) is only approved for horizontal 
terminations.
Diagram 1
Diagram 2