Mounting
Each i
3
 Series detector is supplied with a mounting base that can 
be mounted:
1.  To a single gang box, or
2.  To a 3
1
2
-inch or 4-inch octagonal box, or
3.  To a 4-inch square box with a plaster ring, or
4.  Direct mount or to ceiling using drywall fasteners (Figure 2).
Figure 1: Mounting of Detector
S0121-00
The i
3
 Series heads and bases are keyed so that a 2-wire head will 
only mount to a 2-wire base, and a 4-wire head will only mount 
to  a  4-wire  base.  The  heads  and  bases  are  clearly  identified  as 
either 2-wire or 4-wire. When mounting the i
3
 Series, ensure that 
the head is mounted to the correct base.
Tamper-Resistant Feature
The  i
3
  Series  detectors  include  a  tamper-resistant  feature  that 
prevents  removal  from  the  mounting  base  without  the  use  of  a 
tool. To engage the tamper-resistant feature, cut the small plastic 
tab located on the mounting base (Figure 2), and then install the 
detector. To remove the detector from the base once it has been 
made  tamper  resistant,  use  a  small  screwdriver  to  depress  the 
square tamper release tab, located on the skirt of the mounting 
base, and turn the detector counterclockwise. 
Figure 2: Tamper-Resistant Feature
SNAP OFF TAB
FOR TAMPER LOCK
TAMPER
RELEASE TAB
DIRECT MOUNT
HOLES
S0226-00
Do NOT Install Detectors in the Following Areas:
•  In  or  near  areas  where  particles  of  combustion  are  normally 
present  such  as  kitchens;  in  garages  (vehicle  exhaust);  near 
furnaces, hot water heaters, or gas space heaters.
•  In very cold or very hot areas.
•  In wet or excessively humid areas, or next to bathrooms with 
showers.
•  In dusty, dirty, or insect-infested areas.
•  Near fresh air inlets or returns or excessively drafty areas. Air 
conditioners,  heaters,  fans,  and  fresh  air  intakes  and  returns 
can drive smoke away from the detector.
Consult NFPA 72, the local Authority Having Jurisdiction (AHJ), 
and/or  applicable  codes  for  specific  information  regarding  the 
spacing and placement of smoke detectors. 
CAUTION
Smoke detectors are not to be used with detector guards unless 
the combination has been evaluated and found suitable for that 
purpose.
Wiring Installation Guidelines
All  wiring  must  be  installed  in  compliance  with  the  National 
Electrical Code, applicable state and local codes, and any special 
requirements of the local Authority Having Jurisdiction. 
Proper wire gauges should be used. The conductors used to con-
nect  smoke  detectors  to  the  alarm  control  panel  and  accessory 
devices should be color-coded to reduce the likelihood of wiring 
errors. Improper connections can prevent a system from respond-
ing properly in the event of a fire.
The  screw  terminals  in  the  mounting  base  will  accept  14–22 
gauge  wire.  For  best  system  performance,  all  wiring  should  be 
installed  in  separate  grounded  conduit;  do  not  mix  fire  alarm 
system wiring in the same conduit as any other electrical wiring. 
Twisted pair may be used to provide additional protection against 
extraneous electrical interference.
Wire  connections  are  made  by  stripping  approximately 
1
4
-inch 
of insulation from the end of the feed wire, inserting it into the 
proper base terminal, and tightening the screw to secure the wire 
in place.
Two-Wire Compatibility
System  Sensor  two-wire  smoke  detectors  are  marked  with  a 
compatibility  identifier  located  on  the  label  on  the  back  of  the 
product. For two-wire models 2W-B and 2WT-B, connect detectors 
only to compatible alarm control panels as identified by System 
Sensor’s compatibility chart. This chart contains the current list of 
detectors and UL Listed compatible control units. A copy of this 
list  is  available  from  System  Sensor  upon  request.  NOTE:  Style 
D initiating circuits require the use of a 2W-MOD for models 
2W-B and 2WT-B.
Wiring Diagrams
Figure 3a: Wiring Diagram, 2W-B and 2WT-B
2-WIRE
ZONE
2-WIRE
CONTROL
PANEL
+
2W-B or
2WT-B
(5
) RA
 –
(4
) RA
 +
(3
) – IN/OUT
(2
) + OUT
(1
) + IN
(5
) RA
 –
(4
) RA
 +
(3
) – IN/OUT
(2
) + OUT
(1
) + IN
RA400Z
2W-B or
2WT-B
RA400Z
EOL
RESISTOR
S0133-00