System Sensor 2W-B Manual Do Utilizador

Página de 4
D100-96-00                                                                                               3                                                                                            I56-1800-07R
Figure 3b: Wiring Diagram, 4W-B and 4WT-B
AUX OR
SMOKE
POWER
IDC
4-WIRE
CONTROL
PANEL
+
+
4W-B or
4WT-B
(5
) COM
(4
) NO
(3
) – IN/OUT
(2
) + OUT
(1
) + IN
EOL
RELAY
(A77-716B)
EOL
RESISTOR
4W-B or
4WT-B
(5
) COM
(4
) NO
(3
) – IN/OUT
(2
) + OUT
(1
) + IN
S0134-00
Installation
WARNING
Remove power from alarm control unit or initiating device circuits 
before installing detectors.
NOTE: To install units so that corresponding LEDs are lined up, 
refer to the “Green LED” indicator on the base.
1.  Wire  the  mounting  base  screw  terminals  per  Figure  3a  or 
Figure 3b, as applicable.
2.  Place detector on the base and rotate clockwise. The detector 
will drop into the base and lock into place with a “click”.
3.  After  all  detectors  have  been  installed,  apply  power  to  the 
alarm control unit.
4.  Test each detector as described in Testing.
5.  Reset all the detectors at the alarm control unit.
6.  Notify the proper authorities that the system is in operation.
CAUTION
Dust  covers  are  an  effective  way  to  limit  the  entry  of  dust  into 
the  smoke  detector  sensing  chamber.  However,  they  may  not 
completely  prevent  airborne  dust  particles  from  entering  the 
detector.  Therefore,  System  Sensor  recommends  the  removal  of 
detectors before beginning construction or other dust producing 
activity. When returning the system to service, be sure to remove 
the dust covers from any detectors that were left in place during 
construction.
Testing
Detectors  must  be  tested  after  installation  and  following 
maintenance. 
NOTE: Before testing, notify the proper authorities that mainte-
nance is being performed and the system will be temporarily out 
of service. Disable the zone or system undergoing maintenance to 
prevent any unwanted alarms.
Ensure proper wiring and power is applied. After power up, allow 
80 seconds for the detector to stabilize before testing.
Test i
3
 Series detectors as follows:
A. Test Switch
1.  An  opening  for  the  recessed  test  switch  is  located  on  the 
detector housing (See Figure 4).
2.  Insert a small screwdriver or allen wrench (0.18″ max.) into 
the test switch opening; push and hold.
3.  If  the  detector  is  within  the  listed  sensitivity  limits,  the 
detector’s red LED should light within five seconds.
Figure 4: Recessed Test Switch Opening and SENS-RDR 
Position
PUSH RECESSED
SWITCH WITH A 
0.18
″ MAX.
DIAMETER TOOL
LED
RECESSED TEST SWITCH
POSITION SENS-RDR
AT AN ANGLE ON THE
OVAL AREA OR AT THE
CHAMBER OPENING
BY THE WORD “PAINT”
S0135-00
B.  Smoke Entry Test
  Hold a smoldering punk stick or cotton wick at the side of the 
detector and gently blow the smoke through the detector until 
it alarms.
C. Direct Heat Method (models 2WT-B and 4WT-B only)
  Using a 1000-1500 watt hair dryer, direct the heat toward either 
of the thermistors. Hold the heat source about 12 inches from 
the detector to avoid damage to the plastic. 
NOTE: For the above tests, the detector will reset only after the 
power source has been momentarily interrupted.
If  a  detector  fails  any  of  the  above  test  methods,  its  wiring 
should  be  checked  and  it  should  be  cleaned  as  outlined  in  the 
Maintenance  section.  If  the  detector  still  fails,  it  should  be 
replaced.
Notify the proper authorities when the system is back in service.
Loop Verification (models 2W-B and 2WT-B only)
Loop  verification  is  provided  by  the  EZ  Walk  loop  test  feature. 
This feature is for use with i
3
 Series compatible control panels or 
the i
3
 Series 2W-MOD module only. The EZ Walk loop test verifies 
the initiating loop wiring and provides visual status indication at 
each detector.
1.  Ensure proper wiring and power is applied. Wait approxi-
mately six minutes before performing EZ Walk test.
2.  Place control panel or module in EZ Walk Test mode (refer 
to panel manufacturer’s manual or 2W-MOD manual D500-
46-00).
3.  Observe the LEDs on each detector:
Table 3: EZ Walk Test Detector Modes
Green LED
Red LED
Proper Operation
Double blink 5 sec
Out of Sensitivity
Double Blink 5 sec
Freeze Condition
Double Blink 10 sec
NOTE:  The EZ Walk loop test must not be used instead of alarm 
testing.
Maintenance
NOTE: Before performing maintenance on the detector, notify the 
proper authorities that maintenance is being performed and the 
system  will  be  temporarily  out  of  service.  Disable  the  zone  or 
system undergoing maintenance to prevent any unwanted alarms. 
Power must be removed from the detector before performing 
maintenance of any kind.