Installation and Operations Manual
Superior Valve Company
  
 
Replaceable Suction Filter
On many parallel systems, the Superior Valve Co. suction 
filter is installed.
Alco Controls
 
 
 
 
 
Alco Suction Filter
Comparable to the Superior suction filters and interchangeable 
cores.
Table 28. Type AFD (for cleanup)
Replaceable Cartridges -
Head Pressure Control
In a system with variable pressure control the receiver pressure 
is maintained at the desired pressure by supplying discharge 
gas to it through an adjustable outlet regulator. Further power 
savings may be realized by directing only the hot gas to the 
top of the receiver to minimize the mixing of cold liquid and 
hot gas. As a result subcooled liquid is fed to the evaporators 
resulting in increased refrigeration effect and efficiency. Also, 
the amount of hot gas, that would otherwise condense to wary 
liquid, is reduced and a lower cost, smaller regulator can be 
used. In general, only one third of bypass is needed compared 
to mixing the gas and liquid entering the receiver.
Valve Functions
Referring  to  the  Figure  above, Valve  A  is  an  Inlet  Pressure 
Regulator in the liquid drain line from the condenser, and senses 
the condenser pressure. The regulator closes as the condenser 
pressure drops below the set point, thus back-flooding the 
condenser and reducing the inside surface area available for 
condensing. 
Valve B is and Outlet Pressure Regulator in the bypass line 
from  compressor  discharge  to  the  condenser  liquid  drain 
line. This valve senses the receiver pressure and opens when 
this pressure drops below the set point, thus maintaining the 
receiver pressure. 
Valve C is an In-line Check Valve in the liquid drain line to prevent 
higher pressure from backing up into the condenser during low 
ambient conditions when the compressor is idle.
Table 27. Type AF Filter
Replaceable Cartridges -
Table 25. Type F Filter
Replaceable Cartridges -
Table 26. Type DF (for cleanup)
Replaceable Cartridges -
Shell
No.
Catalog
No.
IBCA
No.
Cartridge
OD (in.)
Filter
Area (in
2
.)
2CFA
F25A
51071
1-23/32
66
3CFA
F35A
51072
2-5/8
115
4CFA
F45A
51073
3-17/32
189
5CFA
F55A
51074
4-1/16
270
Shell
No.
Catalog
No.
IBCA
No.
Cartridge
OD (in.)
Filter
Area (in
2
.)
2CFA
DF25A
51053
1-23/32
66
3CFA
DF35A
51059
2-5/8
115
4CFA
DF45A
51060
3-17/32
189
5CFA
DF55A
51061
4-1/16
270
Shell
No.
Filter
Core
Cartridge
OD (in.)
Filter
Area (in
2
.)
BTAS-2
A2F
1-29/32
66
BTAS-3
A3F
2-3/4
115
BTAS-4
A4F
3-3/4
189
BTAS-5
A5F
4-5/16
270
Shell
No.
Filter
Core
Cartridge
OD (in.)
Filter
Area (in
2
.)
BTAS-2
A2F-D
1-29/32
66
BTAS-3
A3F-D
2-3/4
115
BTAS-4
A4F-D
3-3/4
189
BTAS-5
A5F-D
4-5/16
270