Heatcraft Refrigeration Products 25000102 Manual Do Utilizador

Página de 36
Parallel Compressor Systems Installation & Operations Manual, October 2004  
31
Parallel Compressor Systems
Liquid Drain Control Method
This method is ideal for large capacity systems since a smaller 
regulator is required for liquid line than for discharge line.
During warm ambient temperature conditions valves A and 
C will be open and Valve B will be closed. When the ambient 
temperature at the condenser drops, the condenser pressure 
will tend to become lower. As this pressure is reduced, when 
the pressure becomes as low as its setting, Valve A will begin 
to close, thus causing the refrigerant to back up inside the 
condenser tubes, reducing the condensing surface and allowing 
the pressure to be maintained. As Valve A closes, the receiver 
pressure may be reduced by the cold entering liquid to a level 
below the setting of Valve B, which will begin to open to bypass 
sufficient gas to maintain the receiver pressure at the set point 
of Valve B. Check valve C will prevent the high pressure from 
backing up to the condenser when the receiver pressure is 
higher than the condenser pressure, as would be the case 
during shutdown in a system with a warm receiver.
When the condenser pressure builds up to the setting of Valve 
A, it will open allowing liquid to flow to the receiver.
To  describe  it  again,  during  cold  ambient  temperature 
conditions this liquid will be considerably subcooled and will 
tend to lower the receiver pressure. Valve B will sense the drop 
in pressure and open to admit hot gas into the drain line, thus 
pressurizing  and  warming  the  liquid  and  maintaining  the 
receiver pressure.
Recommended Valve Settings
Regulators ordered for a Condenser Pressure Control system for 
use with common refrigerants will be furnished with the ranges 
and factory settings shown in Table 29. Turning the adjusting 
stem in (clockwise) will raise the set point; turning the stem 
out (counterclockwise) will lower the set point. See Table 29 for 
ranges and amount of pressure change per turn.
Valve
Type
Range
Factory
Set Point
Change Per 
Turn
psig kg/cm
2
psig kg/cm
2
psig kg/cm
2
A4A
ARA0 D
75 to
280
5.2 to
19.7
140
9.8
53
3.7
A7A
A7A1
A72
D 75 to
280
5.3 to
19.7
120
8.4
75
5.3
A9
B 80 to
220
5.6 to
15.5
120
8.4
25
1.8
Field Adjustment
Before  final  field  adjustment  of  regulators  for  Condenser 
Pressure Control, the following should be done:
1.   Install gauges to read compressor discharge, condenser and 
receiver pressures.
2.   Fully charge the system.
3.   Have  other  controls  and  components  functioning 
properly.
4.   Have the system as fully loaded as possible.
5.   Final  adjustments  should  be  made  when  the  outdoor 
ambient is below 65°F. Ideally the ambient should be near 
minimum system outdoor temperature to allow the system 
pressures to drop below the regulator pressure settings. 
Before adjusting make sure that all manual opening stems 
on the regulators are set for automatic operation. It may 
be necessary to temporarily deactivate the low pressure 
cut out controls to keep the compressors running during 
adjustment.
6.   The regulators should be preset using information in Table 
29.
7.   When the valves are adjusted with the system operating, 
enough time must be allowed for the system to stabilize. 
Check  the  sight  glass  to  make  sure  sufficient  liquid  is 
supplied to the evaporators.
8.  Turn the condenser fans off to allow the discharge pressure 
to build up. The regulator A should be adjusted to open 
when the pressure reaches the desired control point. Listen 
for flow through regulator A while watching the pressure 
gauge.
To determine the final setting of regulator B, allow the condenser 
fans to run long enough to subcool the liquid supplied to the 
receiver. Adjust the regulator until the desired receiver pressure 
is obtained. Flow through the valve can be determined by 
listening at the valve for gas flow or by feeling the outlet for 
change in temperature. The setting of regulator B should be at 
least 10 psi lower than the setting of regulator A.
Hot Gas Bypass Regulator Adjustment
Discharge  Bypass  Valves  (DVB)  respond  to  changes  in 
downstream  or  suction  pressure. When  the  evaporating 
pressure is above the valve setting, the valve remains closed. 
As the suction pressure drops below the valve setting, the valve 
responds and begins to open. As with all modulating type 
valves, the amount of opening is proportional to the change in 
the variable being controlled - in this case the suction pressure. 
As the suction pressure continues to drop, the valve continues 
to open farther until the limit of the valve stoke is reached.
On refrigeration systems discharge bypass valves are used to 
prevent the suction pressure from going below the minimum 
value determined by the job requirements.
Sporlan Valve Company
   
 
 
Valve Setting and Adjustment
A complete discussion on valve settings is given in Sporlan 
Application Bulletin 90-40. The fully adjustable models ADRS(E)-
2, ADRP(E)-3, and ADRH(E)-6 are available with two adjustment 
ranges - 0/30 and 0/80 psig. The standard factory settings 
for these are 20 and 60 psig, respectively. The ADRI(E)-1-1/4 
is available with a 0/55 psig range and the standard factory 
setting is 28 psig. 
To adjust these valves, remove the cap an turn the adjustment 
nut  with  a  5/16”  hex  wrench  for  fully  adjustable  models 
ADRS(E)-2,  ADRP(E)-3,  and  ADRH(E)-6.  The  ADRI(E)-1-
1/4  model  has  a  3/8”  adjustment  screw  on  top  of  the 
adjustment  housing.  A  clockwise  rotation  increases  the 
setting and a counterclockwise rotation decreases the setting.  
Adjusting these valves can be complicated because the load 
Table 29. Pressure Range, Set Point & 
Charge Per Turn