Heatcraft Refrigeration Products 25000102 Manual Do Utilizador

Página de 36
32  
 
 
 
 
Part # 25000102
Installation and Operations Manual
must be varied during the setting procedure and it is difficult 
to determine exactly when the bypass valve opens unless a 
pressure gauge can be located at the valve outlet. 
Therefore, sufficient load must be available in some form to 
raise the suction pressure above the desired valve setting. Once 
this is accomplished, the load can be slowly decreased until the 
DBV opens (a hissing sound and/or an accompanying pressure 
rise at the outlet connection will indicate that the bypass valve 
has opened).
Alco Controls
 
 
 
 
 
 
Valve Setting and Adjustment
CPHE and DGRE regulators are commonly used to prevent the 
suction pressure from falling below a predetermined set point. 
Complete information about these valves can be found in ALCO 
CONTROLS Catalog 24-D.
The first step after installation is to determine the set point for 
the minimum suction pressure allowable for the application.  
The following procedure should be followed.
1.   Start the system and determine if it is operating properly: 
Install a gauge on the compressor suction line and measure 
the suction pressure after the system has stabilized. To make 
certain that hot gas is not being bypassed, listen to the main 
regulator flow or feel the outlet piping. If the piping is warm, 
this would indicate hot gas is flowing.
2.   Stop  the  flow  of  hot  gas  by  de-energizing  the  hot  gas 
solenoid valve or by turning the power assembly adjusting 
stem full C
ounteRCloCkwise
.
3.   Reduce the evaporator load until the suction pressure lowers 
to the point at which bypass is desired.
4.   If the hot gas solenoid was de-energized to stop hot gas 
flow, make sure it is now energized.
5.   Turn  the  power  assembly  adjusting  stem  in  a C
loCkwise
 
direction until bypass occurs and suction pressure does 
not fall below the predetermined set point. A C
loCkwise
 turn 
of the adjusting stem will increase the pressure setting; a 
C
ounteRCloCkwise
 turn will decrease it. Standard pressure pilot 
is adjustable from 0 to 80 psig, with one complete turn equal 
to approximately 4 psi change. Adjustments should be made 
in small increments, allowing for the system to stabilize after 
each turn.
6.   Vary the evaporator load to test at various conditions that 
the suction pressure does not fall below the predetermined 
set point.
7.   Replace the seal cap on the adjusting stem.
Control Settings
The following tables are for use when mechanical low pressure 
switches are incorporated for rack pressure control. All control 
settings are approximate and should be adjusted for actual 
field conditions and equipment. All settings are based on 10°F 
TD evaporator.
Low Pressure Switch Setting for RMCC
Some systems use a form of electronic control such as CPC’s 
RMCC  solid  state  controller  for  Rack  operation.  On  these 
systems, there is one mechanical low pressure control for each 
suction group that may be on the rack. This control is for backup 
emergency control in the event of a board or other electronic 
component failure. This low pressure control must be set for the 
minimum suction pressure that the rack would be expected to 
operate at to keep from interfering with the RMCC control.
Example, for a low temperature suction group, this control 
should be set for 0 - 2 psig cutout and approximately 10 psig 
cutin. A medium temperature suction group can be set higher. 
In the event that this control is needed to actually control the 
compressors, set the cutin and cutout for the suction pressure 
that you want the compressors to operate to maintain case or 
box temperatures.
NOTE: This low pressure control will generally be 
mounted on a compressor with the braided 
stainless  steel  tubing  connecting  to  the 
appropriate suction group header.
Table 30. Control Settings for R-404A/R-507
Air Temp
°F
EPR
psig
LP C/I
psig
LP C/O
psig
38-42
69
72
64
34-38
64
66
57
34-36
60
62
55
33-35
59
61
53
28-32
55
58
50
24-28
48
50
35
-10-/0
21
24
15
-10-/-5
20
22
14
-15-/-10
15
17
14
-20-/-15
12
15
8
Table 31. Control Settings for R-22
Air Temp
°F
EPR
psig
LP C/I
psig
LP C/O
psig
38-42
54
57
50
34-38
50
48
43
34-36
47
50
41
33-35
45
47
40
28-32
43
45
38
24-28
36
38
25
-10-/0
13
17
8
-10-/-5
11
14
7
-15-/-10
8
10
5
-20-/-15
5
8
2