Weil-McLain PLUS LINE PLUS-E017-A/1206 Manual Do Utilizador

Página de 68
28
Part Number PLUS-E017-A/1206
PLUS LINE
 Indirect-Fired Water Heaters – Series 3
Install boiler-to-water heater piping
Combined space heating/water 
heating applications
1.  Figure 1  shows  recommended  piping  between
 Gas
boiler and PLUS water heater. All show direct connection
of the water heater piping to the boiler because the boiler
circulator shuts down during water heater operation.
2.  Table , page 29, uses the recommended flow rates for the
PLUS water heater and minimum flow rates for the
Gas  boiler  to  provide  recommended  water  heater  piping
and circulator sizing. If using another circulator, verify it is
at least equal to the Taco selection given in Table , page 29.
For  general  information  on  head  loss  through  boiler  and
boiler-to-water heater piping, refer to the
Gas Boiler
Manual.
.
Procedure
:
 
Step 1
:
Select
Gas Boiler model and water heater model
in Table , page 29.
Step 2:  Read  recommended  minimum  flow  rate,  GPM,  in
table.
Step 3:  Read across to find recommended minimum pipe size
for boiler-to-water heater piping.
Step 4:  Read across to find recommended Taco circulator model.
Use a circulator with a pump curve at least equal to the
Taco circulator shown. See Figure 1, page 29 for pump
curves of typical Taco circulators.
Figure 14 
Boiler-to-water heater piping — Combined 
space heating/water heating application
  3  Boiler relief valve (see Boiler Manual for piping details)
  4  Relief valve discharge piping (see Boiler Manual for details)
  5  Water heater circulator — must be at least equal in capacity to circulator 
recommended in Table 3, page 29
  6  Isolation valves
10  Flow/check valve (with weighted seat to prevent gravity circulation)
11  Purge/drain valves
Figure 15 
Boiler-to-water heater piping —  
Dedicated water-heating only application
Dedicated water heating-only 
applications
1.  Figure 1  shows  recommended  piping  between
 Gas
Boiler and PLUS water heater for dedicated water-heating
only applications.
2.
Pipe sizing
:
Table , page 29, provides the recommended minimum pipe
size for boiler-to-water heater piping.
.
Circulator
:
Use the circulator recommended in Table , page 29. Install
the circulator as shown in Figure 1.
.
Procedure
:
 
Step 1
:  Select
 Gas  Boiler  model  and  water  heater
model in Table , page 29.
 
Step 2
:  Read flow rate expected using the circulator speci-
fied inthe last column.
 
Step 3
:  Size connecting piping as listed under “Boiler pip-
ing” in the table.
  3  Boiler relief valve (see Boiler Manual for piping details)
  4  Relief valve discharge piping (see Boiler Manual for details)
  5  Water heater circulator — (see Table 4, page 29)
  8  Expansion tank (diaphragm or bladder type)
  6  Isolation valves
10  Flow/check valve (with weighted seat)
11  Purge/drain valve
20  Fill line to fill valve (item 23)
B2
Gas