Studer Innotec XTH 8000-48 Manual Do Utilizador

Página de 36
STUDER Innotec 
Xtender 
Installation and operating Instructions 
Xtender V1.3 
Page 34 
 
17
  Table of standard configurations 
No. of 
config. 
Denomination / description 
Units Fact. 
value 
Mod.  
value 
1107  Maximum current of the AC source 
30  
 
1108  Undervoltage of the empty battery 
V/cell 
1.93   
1109  Sub-voltage of the charged battery 
V/cell 
1.75   
1110  Restart voltage of the inverter after undervoltage of the battery 
V/cell 
2  
 
1111  Automatic startup at power up 
y/n 
no 
 
1112  Inverter frequency 
Hz 
50  
 
1121  Maximum DC voltage for stopping the Xtender 
V/cell 
2.84   
1126  Source assistance (Smart Boost) permitted 
y/n 
no 
 
1138  Battery charge current 
60 
 
1139  Battery voltage correction according to the temperature 
mV/°C/ 
cell 
-5  
 
1140  Battery maintenance voltage 
V/cell 
2.27   
1143  Voltage 1 to allow a new battery cycle 
V/cell 
2.1 
 
1144  Duration of under voltage 1 to allow a new cycle 
min. 
30 
 
1145  Voltage 2 to allow a new battery cycle 
V/cell 
1.93  
1146  Duration of under voltage 2 to allow a new cycle 
sec. 
180   
1156  Battery absorption voltage 
V/cell 
2.4    
1157  Duration of absorption 
2  
 
1159  Current at end of absorption 
Adc 
10  
 
1161  Minimum interval between absorptions 
 
1187  Sensitivity of the charge detection (100% approx.25W) 
%  
10 
 
1189  Time interval between load search pulses 
sec. 
0.8 
 
1190  Duration of undervoltage of battery before disconnection 
min. 
3  
 
1191  Dynamic compensation for undervoltage 
y/n 
yes 
 
1194  Battery adaptive low voltage allowed 
o/n 
non 
 
1195  Max voltage for adaptive low voltage 
V/cell 
2.08
 
1198  Time elapsing before transfer relay opens 
sec. 
 
1199  ACin voltage causing the opening of the transfer relay 
Vac 
180   
1200  Immediate open critical threshold for the transfer 
Vac 
50  
 
1246  Auxiliary contact 1 activated by voltage 1 {1247} after delays 
{1248} 
y/n yes 
 
1247  Voltage 1under which auxiliary contact 1 is activated 
V/cell 
1.95  
1248  Delays on voltage 1 to activate auxiliary contact 1 
min. 
 
1249  Auxiliary contact 1 activated by voltage 2 {1250} after delays 
{1251} 
y/n yes 
 
1250  Voltage 2 under which auxiliary contact 1 is activated 
V/cell 
 
1251  Delays on voltage 2 to activate auxiliary contact 1 
min. 
10 
 
1252  Auxiliary contact 1 activated by voltage 3 {1253} after delays 
{1254} 
y/n yes 
 
1253  Voltage 3 under which auxiliary contact 1 is activated 
V/cell 
2.05  
1254  Delays on voltage 3 to activate auxiliary contact 1 
min. 
60 
 
1255  Voltage 1above which auxiliary contact 1 is deactivated after delays  V/cell 
2.25  
1256  Delays on voltage {1255} to deactivate auxiliary contact 1 
min. 
60 
 
1258  Auxiliary contact 1 activated by power 1 
y/n 
yes 
 
1259  Power 1 above which auxiliary contact 1 is activated after delays 
120   
1260  Duration of power 1 for activating auxiliary contact 1 
min. 
 
1261  Auxiliary contact 1 activated by power 2 
y/n 
yes 
 
1262  Power 2 above which auxiliary contact 1 is activated after delays 
80 
 
1263  Duration of power 2 for activating auxiliary contact 1 
min. 
 
1264  Auxiliary contact 1 activated by power 3 
y/n 
no 
 
1286 Output 
voltage 
Vac 
230