Справочник Пользователя для hussman IGFP-R3

Скачать
Страница из 33
igfP-R3, R3P-0608
1
Refrigeration
Plumbing
waste outlet and P-tRaP
The waste outlet is located off the center of the case on 
one side allowing drip piping to be run lengthwise under 
the fixture. There are 3 drains in each fixture that can be 
easily located.
1-1/",  1"  and  3/4"  P-TRAPS  and  threaded  adapters 
are supplied with each fixture. The 3 P-TRAPS must be 
installed to prevent air leakage and insect entrance into 
the fixture.
note:   Pvc-dwv solvent cement is recommended. follow the 
manufacturer’s instructions.
installing condensate drain
Poorly  or  improperly  installed  condensate  drains  can 
seriously interfere with the operation of this refrigerator, and 
result in costly maintenance and product losses. Please 
follow the recommendations listed below when installing 
condensate drains to insure a proper installation:
1.   Never use pipe for condensate drains smaller 
than the nominal diameter of the pipe or P-TRAP 
supplied with the case.
.   When connecting condensate drains, the P-TRAP 
must be used as part of the condensate drain 
to prevent air leakage or insect entrance. Store 
plumbing system floor drains should be at least 14" 
off the center of the case to allow use of the P-TRAP 
pipe section. Never use two water seals in series in 
any one line. Double P-TRAPS in series will cause a 
lock and prevent draining.
3.   Always provide as much down hill slope ("fall") as 
possible; 1/8" per foot is the preferred minimum. 
PVC pipe, when used, must be supported to 
maintain the 1/8" pitch and to prevent warping.
4.   Avoid long runs of condensate drains. Long runs 
make it impossible to provide the "fall" necessary for 
good drainage.
5.   Provide a suitable air break between the flood rim of 
the floor drain and outlet of condensate drain. 1" is 
ideal.
6.   Prevent condensate drains from freezing:
a. Do not install condensate drains in contact with 
non-insulated suction lines. Suction lines should 
be insulated with a non - absorbent insulation 
material such as Armstrong's Armaflex.
b. Where condensate drains are located in dead 
air spaces (between refrigerators or between a 
refrigerator and a wall), provide means to prevent 
freezing. The water seal should be insulated to 
prevent condensation.
Refrigerant type
The  standard  refrigerant  will  be  R-  unless  otherwise 
specified on the customer order. Check the serial plate on 
the case for information.
Piping
The  refrigerant  line  outlets  are  located  under  the  case. 
Locate first the electrical box, the outlets are then on the 
same side of the case but at the opposite end. Insulate 
suction lines to prevent condensation drippage.
Refrigeration lines
Liquid 
Suction
3/8” O.D.
5/8” O.D. 
note:   the standard coil is piped at 
5
/
8
” (suction); however, 
the store tie-in may vary depending on the number of 
coils and the draw the case has. depending on the case 
setup, the connecting point in the store may be 
5
/
8
”, 
7
/
8
”, 
or 1
1
/
8
”. Refer to the particular case you are hooking up.
Refrigerant  lines  should  be  sized  as  shown  on  the 
refrigeration legend furnished by the store.
Install 
P-tRaPS (oil traps) at the base of all suction line 
vertical risers.
Pressure drop can rob the system of capacity. To keep the 
pressure drop to a minimum, keep refrigerant line run as 
short as possible, using the minimum number of elbows. 
Where elbows are required, use long radius elbows only.
control Settings
See  R3,  R3P  technical  data  sheet  for  the  appropriate 
settings for your merchandiser. Maintain these parameters 
to achieve near constant product temperatures. Product 
temperature should be measured first thing in the morning, 
after  having  been  refrigerated  overnight.  Defrost  times 
should be as follows: OFF CYCLE - Defrost times should 
be as directed in the R3, R3P technical data sheet. The 
number of defrosts per day and the duration of the defrost 
cycle may be adjusted to meet conditions present at your 
location.
access to tX valves and drain lines
Mechanical - Remove product from end of case. Remove 
product  racks.  Remove  refrigeration  and  drain  access 
panels (labeled). TX valve (mechanical only) and drain are 
located under each access panel at end of the case.
electronic - The Electronic Expansion valve master and 
slave cylinder(s) are located within the electrical access 
panel(s).