EMO 500   -   RATIO FEEDBACK MODE
 
 
     
The EMO 500 also features a Ratio Feedback Mode of operation in which the Ideal 
Ratio and the Actual Measured Ratio are compared and a 4-20 mA signal will be 
generated to control one of the Flow Rates.  This will maintain the programmed Ideal 
Ratio over a wide range of flow rates. 
      
     The formula used to determine the correct analog output is as follows:
 
 
                                                    
    
Analog Output = Half Range + (Ideal Ratio-Actual Ratio) * Gain   
 
     The Half Range refers to the middle point of the Analog Output.  If the output varies 
from 0 to 20mAmp. the half point will be 10mAmp..  If the Analog Offset is set to give 
an output of 4 to 20mAmp. the Half Point will be 12mAmp. 
 
 
To use the Ratio Feedback Mode the user should enter 07 as the Analog Rule (See P.18)
        
 
 
     NOTE: The Ratio Feedback Mode w/Reset works in exactly the same manner 
excepting that the analog output will go to the start point (mid-point) on Reset All input.