 228
Hardware configuration
Section 6: Meter operation
 Reference, Installation, and Operations Manual
June 2013
3-9000-743 Rev S
6.5.1
Hardware configuration
The Daniel Mark III Ultrasonic Gas Flow Meter communicates serially with the Daniel GC using 
Option Board Port C in either RS-232 or RS-485 (half duplex) mode. Refer to 
 in 
 for further information on connecting the two devices.
6.5.2
Software configuration
It is recommended that the Daniel MeterLink 
Field Setup Wizard
 be used to configure the GC 
interface (
).
The 
GasPropertiesSrcSel data point is used to select whether the gas property data is live (read 
from a GC) or fixed. The 
GCSerialPort data point is used to either disable the GC interface or 
select (Option Board) Port C for communicating with the GC. These two points are 
automatically set via the Daniel MeterLink 
Field Setup Wizard
.
The following information is required in order to configure the Daniel Mark III Ultrasonic Gas 
Flow Meter to interface with a GC:
the GC Modbus communication configuration:
protocol (
GCProtocol
)
baud rate (
GCBaud
)
Modbus address (
GCModbusID
)
the desired stream number (
GCStreamNumber) and the length of time to wait for the 
desired stream number (
GCDesiredStreamTimeout), and
heating value configuration:
type of heating value (
GCHeatingValueType
)
 unit (
GCHeatingValueUnit
)
The software configuration also allows for the selection of how the meter is to respond when 
the GC-read data is considered invalid (
GasPropertiesSrcSelGCAlarm): whether to ‘freeze’ the 
‘in-use’ gas property data to the last good GC-read data or to use fixed gas property data 
instead.
The length of time to wait for the desired stream (
GCDesiredStreamTimeout) is not 
configurable within the Daniel MeterLink 
Field Setup Wizard
. It is, however, configurable using 
the Daniel MeterLink 
Edit/Compare Configuration
 utility. Its default value is 100 minutes and 
limits are [6, 255 min]. The total number of streams and the update time per stream should be 
taken into account when updating this parameter.
6.5.3
Gas property data
The gas property data read from the GC includes gas composition, heating value, and specific 
gravity (relative density).
The gas composition includes the 21 standard components plus 
C
6
+ and Neopentane (
 for a list of data point names). Refer t
 for further information on how 
the GC-read gas properties are mapped to the ‘in-use’ gas property data points.
The GC-read heating value and specific gravity are stored in the 
HeatingValueGC and Specific-
GravityGC data points, respectively.