Bosch ICP-CC488 用户手册

下载
页码 118
ICP-CC488 | Installation Guide | 19.0  
Partitioning 
EN | 86 
 
 
Bosch Security Systems, Inc. | 12/08 | F01U089457-02 
 
19.4.1 
Zone Allocations for Areas 1 and 2 
 
Location 
502 to 517 
 Location 
Default 
Zone 1 LED – Area 1 Codepad
 
502
 
0
 
Zone 2 LED – Area 1 Codepad
 
503
 
0
 
Zone 3 LED – Area 1 Codepad
 
504
 
0
 
Zone 4 LED – Area 1 Codepad
 
505
 
0
 
Zone 5 LED – Area 1 Codepad
 
506
 
0
 
Zone 6 LED – Area 1 Codepad
 
507
 
0
 
Zone 7 LED – Area 1 Codepad
 
508
 
0
 
Zone 8 LED – Area 1 Codepad
 
509
 
0
 
Zone 1 LED – Area 2 Codepad
 
510
 
0
 
Zone 2 LED – Area 2 Codepad
 
511
 
0
 
Zone 3 LED – Area 2 Codepad
 
512
 
0
 
Zone 4 LED – Area 2 Codepad
 
513
 
0
 
Zone 5 LED – Area 2 Codepad
 
514
 
0
 
Zone 6 LED – Area 2 Codepad
 
515
 
0
 
Zone 7 LED – Area 2 Codepad
 
516
 
0
 
Zone 8 LED – Area 2 Codepad
 
517
 
0
 

Not mapped for this LED 
A zone is mapped to this LED 
You can enable or disable the zone allocations for 
Area 1 and Area 2.  For example, if the location 507 
is set to “0”, the zone LED of Area 1 is not mapped. 
Detailed Example 
In the following example, Zones 1, 2, 3, and 4 are 
allocated to Area 1 to appear as zones 1, 2, 3 and 4. 
Zones 1, 5, 6, 7, 8 are allocated to Area 2 to appear 
as zones 1, 5, 6, 7, and 8. Programming the same 
zone into more than one area specifies that zone as a 
common zone. 
 
Figure 18:  Area 1 Codepad Display 
Area 1 Zone Allocations 
Locations 502 to 509: 1  2  3  4  0  0  0  0 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Figure 19:  Area 2 Codepad Display 
Area 2 Zone Allocations 
Locations 510 to 517: 1  0  0  0  5  6  7  8 
 
19.5  User Code Allocations 
Location
534 to 549 
 Location 
Default 
User Code 1 
534 
User Code 2 
535 0 
User Code 3 
536 0 
User Code 4 
537 0 
User Code 5 
538 0 
User Code 6 
539 0 
User Code 7 
540 0 
User Code 8 
541 0 
User Code 9 
542 0 
User Code 10 
543 0 
User Code 11 
544 0 
User Code 12 
545 0 
User Code 13 
546 0 
User Code 14 
547 0 
User Code 15 
548 
User Code 16 
549 
Locations 534 to 549 are used to assign each User 
Code to one or two area areas of a partitioned ICP-
CC488 Control Panel. Enter a value from 0 to 3 into 
each of these locations to assign the User Code 
holder to the areas it must operate (refer to Table 61). 
You can allocate multiple User Codes to the same 
area. 
Table 61:  User Code Allocations 
 
Option 
Description 
Not allocated to an area 
Allocated to Area 1 
Allocated to Area 2 
Allocated to Area 1 and Area 2 
19.6  Setting Up and Programming 
Codepads for Partitioning 
Only the CP5 Area Addressable (CP500A) and CP5 
Master Partitioned (CP500P) codepads can be used 
with a partitioned ICP-CC488 Control Panel.