SPYDER® BACNET® PROGRAMMABLE CONTROLLERS
63-2689—05
18
Fig. 21. Controller wiring diagram (model PUB6438S shown) with 4 to 20 mA heating, cooling, and model ML6161 damper 
actuator. (For note 2, refer to Fig. 14.)
COM
COM
DO4
COM
UI-6
FAN
SERIES 70 
VALVE 
ACTUATOR
24
VAC
IN-
PUT
COM
TWO - OR 
THREE-WAY
CHILLER 
WATER VALVE
SERIES 70 
VALVE 
ACTUATOR
24
VAC
IN-
PUT
COM
TWO - OR 
THREE-WAY
HOT WATER/
STEAM VALVE
AO-3
3
ML6161 D
AMPER
ACTU
AT
OR
CW
COM
CCW
DAMPER OPEN
DAMPER CLOSED
DISCHARGE 
AIR TEMP
AO-2
AO-1
UI-2
UI-1
DI-1
UI-3
AO-1 COM AO-2 AO-3 COM
UI-1 COM UI-2 UI-3 COM UI-4 UI-5 COM UI-6
DI-1 DI-2 COM DI-3
20V DC
DI-4
24 V
AC
24V
AC COM
DO-1
COM
DO-2
DO-3 DO-4
DO-5
COM
DO-6 COM
12345678
1
0
9
2345678 0
9
1
1 1111111 2
1
12345678 0
9
2
2 2222222 3
3
12345678 0
9
3
3
3
3
3
3
3
3 4
DO-7 DO-8 COM
BAC–
BAC+
SHIELD
BACnet MS/TP+
BACnet MS/TP–
SHLD
EGND
SBUS1 SBUS2
2
1
3
EARTH GROUND WIRE LENGTH SHOULD BE HELD TO A MINIMUM.  USE THE HEAVIEST GAUGE WIRE AVAILABLE, UP TO 14 AWG (2.O MM
2
) WITH 
A MINIMUM OF 18 AWG (1.O MM
2
), FOR EARTH GROUND WIRE.
TO ASSURE PROPER ELECTRICAL CONTACT, WIRES MUST BE TWISTED TOGETHER BEFORE INSERTION INTO THE TERMINAL BLOCK.
CONTACTS MUST BE SUITABLE FOR DRY SWITCHING, 5V AT 10 mA.  USE SEALED TYPE, GOLD FLASHED OR PIMPLED CONTACTS.
M31178A
4
DIP SWITCH S3
(TR23 AND
TR24 ONLY.)
ON
SW1 SW2 SW3
DIP SWITCH S2
ON
SW1 SW2
DIP SWITCH
S1
ON
SW1 SW2
DIP SWITCH S1 FOR HUMIDITY MODELS ONLY.  SEE TR23 INSTALLATION INSTRUCTIONS, FORM NO. 62-0267, FOR CONFIGURATION DETAILS.
TR23-H ONLY
DO NOT
CHANGE THIS 
SWITCH
POSITION.
10
8
6
4 3
GND
SENSOR
LON +
LON -
SETPT
LED
O
VERRIDE
HUM
24 V
AC
9
24 VAC
24 VAC
COM
+-
1
COM
2
5
7
11
12
1