SPYDER® BACNET® PROGRAMMABLE CONTROLLERS
63-2689—05
20
Table 8. Status LED States.
BACNET STATUS LED:
The LED on the front of the controller, between the BACnet 
MS/TP terminals and MAC Address DIP Switches, provides a 
visual indication of the BACnet MS/TP communication status. 
When the controller receives power, the LED appears in one of 
the following allowable states, as described in Table 9.
Table 9. BACnet Status LED States.
Step 3. Checkout Completion
At this point the controller is installed and powered. To 
complete the checkout, the N
IAGARA
 F
RAMEWORK
® application 
(run on a PC) is used to configure the I/O and functions of the 
controller. Refer to the Programming Tool User Guide, form no. 
63-2662, for controller configuration and programming details.
CONTROLLER REPLACEMENT
There are no serviceable or repairable parts inside the 
controller.
WARNING
Fire, Explosion, or Electrical Shock Hazard.
Can cause severe injury, death or property damage.
Do not attempt to modify the physical or electrical 
characteristics of this device in any way. Replace the 
controller if troubleshooting indicates a malfunction.
WARNING
Electrical Shock Hazard.
Can cause severe injury, death or property damage.
Disconnect power supply before beginning controller 
replacement to prevent electrical shock or equipment 
damage.
Terminal Block Removal
To simplify controller replacement, all terminal blocks are 
designed to be removed with the wiring connections intact and 
then re-installed on the new controller. See Fig. 24 and refer to 
the following procedure:
IMPORTANT
To prevent bending or breaking the alignment pins on 
longer terminal blocks, insert the screwdriver at 
several points to evenly and gradually lift up the 
terminal block.
Insert the screwdriver blade no more than 1/8 in. 
(3 mm) to prevent damage to the terminal block align-
ment pins on the controller circuit board.
Fig. 24. Removing Terminal Blocks.
1. Use a thin-bladed screwdriver to evenly raise the 
terminal block from its alignment pins:
a. For short terminal blocks (1 to 5 terminals), insert 
screwdriver blade in the center of the terminal block 
and use a back and forth twisting motion to gently 
raise the terminal block from its alignment pins 1/4 in. 
(6.35 mm).
b. For long terminal blocks (6 or more terminals), insert 
screwdriver blade on one side of the terminal block 
and gently rotate the blade 1/4 turn. Then, move to 
the other side of the terminal block and do the same. 
Repeat until the terminal block is evenly raised 1/4 in. 
(6.35 mm) from its alignment pins.
LED State
Blink Rate
Status or Condition
OFF
Not applicable
No power to processor, 
LED damaged, low 
voltage to board, first 
second of power up or 
loader damaged.
ON
ON steady; 
not blinking
Processor not operating. 
Application Program CRC 
being checked. This takes 
1-2 seconds and occurs 
on each restart (power 
up, reset and reflash, and 
following configuration file 
download).
Very Slow Blink
(continuous)
1 second ON,
1 second OFF
Controller is operating 
normally.
Slow Blink
(continuous)
0.5 second ON,
0.5 second OFF
Controller alarm is active 
or controller in process of 
configuration file 
download.
Medium Blink
(continuous)
0.3 second ON,
0.3 second OFF
Controller is in reflash 
mode or awaiting/
receiving reflash data via 
the BACnet network.
BACnet LED Status
Status or Condition
Solid on
Controller has power, loader is not 
running.
Solid on, blinking off 
once in 2.5 sec.
Controller is in reflash mode, no MS/
TP communication.
Solid on, blinking off 
twice in 2.5 sec.
Controller is in reflash mode, MS/TP 
communication present.
Solid on, blinking off 
thrice in 2.5 sec
Controller is in reflash mode, MS/TP 
communication data transfer in 
progress.
Solid off, there is no 
power
No power to processor, LED 
damaged, low voltage to board, or 
loader damaged.
Solid off, blinking on 
once in 2.5 sec.
Controller is running, no MS/TP 
communication.
Solid off, blinking on 
twice in 2.5 sec.
Controller is running, MS/TP 
communication present.
Solid off, blinking on 
thrice in 2.5 sec
Controller is running, MS/TP 
communication data transfer in 
progress.