Honeywell MRP-2001E Benutzerhandbuch

Seite von 136
Master Programming Level
Programming
MRP-2001 & MRP-2001E   PN 53040:A  4/16/2007
65
Pressing 3 for System Setup, while viewing Programming Screen #2, will cause the following 
screens to be displayed: 
3.5.6.1  Timers
Timers for Soak, Waterflow Delay and AC Loss Delay can be programmed by pressing 2 while 
viewing System Setup Screen #1.  The following screen will be displayed: 
  PROGRAMMING
1=CROSS INPUT ZONES
2=ON-BOARD RELAYS
3=SYSTEM SETUP
Programming Screen #2
    SYSTEM SETUP
1=FUTURE USE
2=TIMERS
3=BANNER
System Setup Screen #1  
    SYSTEM SETUP
1=TIME-DATE
2=TROUBLE REMIND  NO
3=CHARGR DISABLE  NO
System Setup Screen #2  
   SYSTEM SETUP
1=ABORT TYPE
2=TIMERS
3=BANNER
System Setup Screen #1
      TIMERS
1=SOAK  1        1 MIN
2=SOAK  2        2 MIN
3=WATERFLOW DELAY  60S
Timer Screen #1  
      TIMERS
1=AC LOSS DELAY  2 HR
Timer Screen #2