3.5.6.1.1 Soak 1 or Soak 2
The factory default setting for Soak Time is 10 minutes.  To select a Soak Time delay of 10 to 
30 minutes, press 1 for Soak 1 (Release Circuit 1) or 2 for Soak 2 (Release Circuit 2) while 
viewing Timer Screen #1.  The following display will appear:
Pressing 1 while viewing the Soak Time Setup Screen will program the corresponding releasing 
circuit to remain on during alarm activation until the alarm is cleared and the panel is reset.
Pressing 2 while viewing the Soak Time Setup Screen will display the following screen: 
This screen allows the user to program a specific length of time for the releasing circuit to 
remain active after an input initiating a release has cleared.  A flashing cursor is positioned in 
the lower left corner of the display.  Enter a soak time consisting of two digits, such as 10 for ten 
minutes.  Upon entering the second digit, the time delay will be stored in the control panel 
memory and the display will return to the Delay Screen which will indicate the new soak time.  
In this example, when the input circuit which initiated a release has cleared, the soak timer will 
start, allowing the releasing circuit to continue releasing water for a total of ten minutes and 
then deactivate.
3.5.6.1.2 Waterflow Delay
A delay can be added prior to declaring a waterflow type of alarm.  Be careful to include any 
built-in delays of the waterflow device.  The factory default setting for Waterflow delay is 00 
for no delay.  To select a Waterflow delay of 01 to 90 seconds for all devices programmed for 
Waterflow delay, press 3 while viewing Timer Screen #1 to display the following screen:
A flashing cursor is positioned in the lower left corner of the display.  Enter a delay time 
consisting of two digits, such as 25 for twenty-five seconds.  Upon entering the second digit, the 
time delay will be stored in the control panel memory and the display will return to the Delay 
Screen which will indicate the new delay time.
     SOAK # TIME
1=ALWAYS ON
2=ENTER MINUTES
Soak Time Setup Screen  
     SOAK # TIME
RANGE 10-30 MINUTES
Soak Time Screen  
     TIMER
1=SOAK 1      1 MIN
2=SOAK 2      2 MIN
3=WATERFLOW DELAY 0 S
Timer Screen #1
  WATERFLOW DELAY
RANGE 00-90 SECONDS