3.5.6.1.3 AC Loss Delay
The reporting of a loss of AC power can be delayed by programming the length of the desired 
delay.  Press 1 while viewing Timer Screen #2 to display the following: 
A flashing cursor will appear in the lower left corner of the display.  The factory default setting 
is 02 hours.  Type the two digit AC loss reporting delay in hours (00 to 24 hour delay).  When 
the second digit is entered, the display will return to AC Loss Delay Screen #1.
Note:  Upon the loss of AC power at the control panel, relays programmed for AC Loss will 
transfer immediately, regardless of the AC Loss Delay setting.  If no troubles other than AC 
Loss exist in the panel, the System Trouble relay will delay activation for the duration of the AC 
Loss Delay
 setting.
3.5.6.2 Banner
The top line of the display, which appears when the control panel is in normal mode, can be 
changed by using the Banner option.  Pressing 2 while viewing System Setup Screen #1 will 
cause the following to be displayed: 
Pressing 1 while viewing the Select Banner Screen will display the following screen:
This screen allows the user to select the factory default Banner which will be displayed when 
the system is in Normal Mode of operation.  Press the Enter key to accept this as the default 
display.  Press the Escape key to cancel and return to the Select Banner Screen.
     TIMER
1=AC LOSS DLAY 2 HR
Timer Screen #2
 AC LOSS DELAY
RANGE 00-24 HOURS
AC Loss Delay Screen #1  
   SYSTEM SETUP
1=ABORT TYPE
2=TIMERS
3=BANNER
System Setup Screen #1
   SELECT BANNER
1=FACTORY BANNER
2=USER BANNER
Select Banner Screen  
   FACTORY BANNER
      
    
 PRESS ENTER IF OK
User Defined Banner Screen #1