Honeywell MRP-2001E Benutzerhandbuch

Seite von 136
Maintenance Programming Level
Programming
MRP-2001 & MRP-2001E   PN 53040:A  4/16/2007
83
Pressing 1 while viewing the History screen will cause the following screen to be displayed:
To view all the events which have occurred in the control panel since the history file was last 
erased, press 1 while viewing the Events screen.  To view only alarms which have occurred, press 2 
while viewing the Events screen.  To view events other than alarms, press 3.  The most recent event 
will be displayed on the screen.  To view all of the selected events, press the up or down arrow keys 
to scroll through the list of events.  If no events have occurred, the display will read NO EVENTS 
IN HISTORY
.  
Pressing 2 while viewing the History Screen will cause the following screen to be displayed: 
Pressing 1 while viewing the Erase History Screen will cause the message ERASING HISTORY, 
PLEASE WAIT
 to be displayed.  The display will then return to the History Screen.  Pressing 2 will 
cause the display to return to the History Screen without erasing the History file.
3.6.3 Walktest 
To perform a walktest, press 3 while viewing Maintenance Screen #1.  The following screen will be 
displayed:
The operator can press 1 to perform a silent walktest or 2 to perform an audible walktest.  The 
display will read UNIT IN WALKTEST.  To end the Walktest, press the Esc (Escape) key.
Pressing 3 after the walktest has been completed, will allow the operator to view the results of the 
walktest.
      HISTORY
1=VIEW ALL
2=VIEW ALARMS
3=VIEW OTHER EVENTS
    ERASE HISTORY
      PROCEED ?
1=YES            2=NO
Erase History Screen   
    PROGRAMMING
1=INPUT ZONES
2=HISTORY
3=WALKTEST
Maintenance Screen #1
     WALKTEST
1=SILENT
2=AUDIBLE
3=VIEW EVENTS
Walktest Screen