Monessen Hearth EYF18 Benutzerhandbuch

Seite von 32
65D1009
10
EYF Series Unvented Gas Log Set
INSTALLATION
The gas log heater must be installed at least 5" above any 
combustible  flooring  material,  such  as  carpeting  or  tile, 
which is closer than 14" to the base of the fireplace. The 
minimum distance must be maintained from the top surface 
of carpeting, tile, etc. Figure 9
OR,
The gas log heater may be installed nearer to the floor if a 
minimum of 14" of noncombustible material such as slate 
or marble is installed between the base of the fireplace and 
the combustible flooring. Figure 10
5” Min.
FP2536
floor clear comb
Heater in Fireplace 
or firebox
Combustible 
Material
Figure 9 - 
Minimum Clearance Above Combustible Flooring
FP536
14” Min.
FP2537
floor clear noncomb 
Heater in Fireplace or 
Firebox
This Distance May 
Now be Less than 5"
Combustible 
Material
FP537
Figure 10 -
Minimum Clearance above Combustible Flooring with 
Noncombustible Material Installed at Base of Fireplace
FLOOR CLEARANCE
FIREPLACE PREPARATION
BEFORE FULLY INSTALLING THE UNIT:
•  
Turn OFF the gas supply to the fireplace or firebox.
•  
Seal  any  fresh  air  vents  and/or  ash  clean-out  doors 
located on the floor or wall of the fireplace. If left un-
sealed, drafting may cause pilot outage or sooting. Use 
a heat resistant sealant. Do not seal the chimney flue 
damper.
INSTALLING VENTED APPLICATIONS
Manual and millivolt controlled gas logs may be installed as 
a vented decorative log set in compliance with ANSI Z1.60 
and National Fuel Gas Code, Section 6.6 Since, the gas 
logs are operated with the damper open, non-combustible 
material and minimum mantel requirements do not apply.
BEFORE INSTALLING THE APPLIANCE:
•  
Turn off gas supply to fireplace or firebox.
•  
Have  the  fireplace  floor  and  chimney  professionally 
cleaned to remove ashes, soot, creosote or other ob-
structions. Have this cleaning performed annually after 
installation.
•  
Seal any fresh air vents or ash clean-out doors located 
on floor or wall of fireplace. If not, drafting may cause 
pilot outage or sooting. Use a heat-resistant sealant. 
Do not seal chimney flue damper.
Install  and  operate  the  appliance  as  directed  in  this 
manual.
W
ARNING
Before  installing  in  a  solid  fuel  burning 
fireplace, The chimney flue and firebox must 
be  cleaned  of  soot,  creosote,  ashes  and 
loose paint by a qualified chimney cleaner.
W
ARNING
This appliance is for installation only in a solid 
fuel burning fireplace (masonry fireplace or 
manufactured  fireplace)  with  a  working 
flue  and  constructed  of  noncombustible 
material.
Exception:  
DO  NOT  install  this  appliance 
in  a  factory-built  fireplace  that  includes 
instructions  stating  that  it  has  not  been 
tested or should not be used with unvented 
gas logs.