EYF Series Unvented Gas Log Set
NOTICE: A qualified gas appliance installer must connect 
the heater to the gas supply. Consult all local codes.
IMPORTANT: Hold heater valve firmly with a wrench to 
prevent movement when connecting to inlet pipe. 
Always use an external regulator for all propane/LPG 
heaters and high pressure one to two-pound systems 
only
, to reduce the supply tank pressure to a maximum of 
13" w.c. This is in addition to the internal regulator in the 
heater valve.
GAS LINE CONNECTION
W
ARNING
Use new black iron or steel pipe. Internally tinned copper or copper tubing can 
be used per National Fuel Code, section 2.6.3, providing gas meets hydrogen 
sulfide limits, and where permitted by local codes. Gas piping system must be 
sized to provide minimum inlet pressure (Listed on Data Plate) at the maximum 
flow rate (BTU/Hr). Undue pressure loss will occur if the pipe is too small.
A manual shutoff valve must be installed upstream of the appliance. Union tee 
and plugged 1/8" NPT pressure tapping point should be installed upstream of 
the appliance. Figure 13
FP2371
gas connect
Stainless 
Flexible 
Tube
Pipe
Possible Locations 
for Pressure 
Tapping Point
Gas 
Supply 
Inlet
To 
Heater 
Valve
Pipe 
Coupling
Manual Shutoff 
Valve
FP371
Figure 13 - 
Gas Connection
CHECk GAS TYPE: The gas supply must 
be the same as stated on the heater’s rat-
ing plate. If the gas supply is different, DO 
NOT INSTALL THE HEATER. Contact your 
dealer for the correct model.
Connecting  directly  to  an  unregulated 
propane/LPG  tank  can  cause  an  explo-
sion.
W
ARNING
W
ARNING
The heater gas inlet connection is a 3/8" NPT at the valve. 
All units  have the inlet connection on the right side, when 
you face the unit. To connect from the opposite side, route 
the pipe under the rear portion of the unit.
When tightening up the joint to the valve, hold the valve 
securely to prevent movement. 
MANUAL CONTROL
 
Figure 14
The  pressure  regulator  is  preset  and  locked  to  dis-
courage tampering. 
If the pressure is not as specified, 
replace the regulator with the correct part from the parts 
list in this manual.
Remove 1/8" NPT plug, locat-
ed on side of regulator body. 
Install fitting and tubing to 
pressure  gauge.  After 
taking pressure reading, 
reinstall  test  plug. 
Check  for  gas 
leaks.
FP2499
manual valve
NPT Test Plug
FP499
Figure 14 - 
Pressure Test Point Location for 
Manual Control
MILLIVOLT CONTROL
 
Figure 15
The valve regulator con-
trols the burner pressure 
which should be 
checked at the pres-
sure test point.
Turn  captured  screw 
counter clockwise two 
or  three  turns  and 
then  place  tubing  to 
pressure  gauge  over 
test  point  (Use  test 
point “OUT” closest 
to control knob). Af-
ter  taking  pressure 
reading, be sure and turn captured screw clockwise firmly 
to re-seal. Do not over torque. Check for gas leaks.
Figure 15 - Pressure Test Point Location
Millivolt Control
 
FP2372
millivolt valve
Test Port "OUT"
FP37