EYF Series Unvented Gas Log Set
INSTALLATION INFORMATION
ADEQUATE COMBUSTION AND VENTILATION AIR
This heater shall not be installed in a confined space or unusually tight construction unless 
provisions are provided for adequate combustion and ventilation air.
The National Fuel Gas Code, (ANSI Z223.1/NFPA54), defines a confined space as a space 
whose volume is less than 50 cubic feet per 1,000 BTU per hour (4.8 m
3
 per kw) of the aggre-
gate input rating of all appliances installed in that space, and an unconfined space as a space 
whose volume is not less than 50 cubic feet per 1,000 BTU per hour (4.8 m
3
 per kw) of the 
aggregate input rating of all appliances installed in that space. Rooms communicating directly 
with the space in which the appliances are installed, through openings not furnished with doors, 
are considered a part of the unconfined space.
UNUSUALLy TIGhT CONSTRUCTION IS DEfINED AS CONSTRUCTION WhERE:
a) walls and ceilings exposed to the outside atmosphere have a continuous water vapor re-
tarder with a rating of 1 perm  
(6 x 10
11
 kg per pa/sec-m
) or less with openings gasketed or sealed;
b) weather striping has been added on openable windows and doors, and
c) caulking or sealants are applied to areas such as joints around window and door frames, 
between sole plates and floors, between wall-ceiling joints, between wall panels, at pen-
etrations for plumbing, electrical, and gas lines, and at other openings. 
x 1000
x 1000 = 5800 BTU/hr
x 1000 = 9,760 BTU/hr
BTU/hr = 
BTU/hr = 
BTU/hr = 
The following formula can be used to determine the maximum heater rating per the definition 
of unconfined space:
(L
1
 + L
) Ft x (W) Ft x (H) Ft 
50
Consider two connecting rooms with an open area between, with the following dimensions: 
L
1
 = 15Z\x Ft., L
 = 1 Ft., W = 1 Ft., H = 8 Ft.
(15Z\x
 
 + 1) x (1) x (8)
50
If there were a door between the two rooms the calculation would be based only on the room 
with the heater.
(15Z\x) x (12) x (8)
50
W
H
FP2439
combustion air
Room Divider
Fireplace
Figure 1 - 
Example of a Large Room with a Room 
Divider
FP439
W
ARNING
If  the  area  in  which  the  heater  may  be
operated  is  smaller  than  that  defined  as
an  unconfined  space  or  if  the  building  is
of  unusually  tight  construction,  provide
adequate combustion and ventilation air by
one of the methods described in the National
fuel Gas Code, ANSI Z223.1/NfPA54, Section
5.3 or applicable local codes.