GAS SUPPLY
Recommended Gas Pipe Diameter
Pipe Length 
(Feet)
Schedule 40 Pipe 
Inside Diameter
Tubing, Type L 
Outside Diameter
Nat.
LP
Nat.
LP
0-10
1/2”
1.3cm
3/8”
1.0cm
1/2”
1.3cm
3/8”
1.0cm
10-40
1/2”
1.3cm
1/2”
1.3cm
5/8”
1.6cm
1/2”
1.3cm
40-100
1/2”
1.3cm
1/2”
1.3cm
3/4”
1.9cm
1/2”
1.3cm
100-150
3/4”
1.9cm
1/2”
1.3cm
7/8”
2.2cm
3/4”
1.9cm
Note: Never use plastic pipe. Check to confirm whether your lo-
cal codes allow copper tubing or galvanized.
Note: Since some municipalities have additional local codes, it is 
always best to consult your local authority and installation code.
The use of the following gas connectors is recommended:
– ANS Z21.24 Appliance Connectors of Corrugated Metal Tub-
ing and Fittings
– ANS  Z21.45 Assembled  Flexible Appliance  Connectors  of 
Other Than All-Metal Construction
The above connectors may be used if acceptable by the authority 
having jurisdiction. The state of Massachusetts requires that a flex-
ible appliance connector cannot exceed three feet in length.
Figure 1
Consult the current National Fuel Gas Code, ANSI Z223.1 CAN/
CGA-B149 (.1 or .2) installation code.
Installing a New Main Gas Cock
Each appliance should have its own manual gas cock.
A manual main gas cock should be located in the vicinity of the unit. 
Where none exists, or where its size or location is not adequate, contact 
your local authorized installer for installation or relocation.
Compounds used on threaded joints of gas piping shall be resistant 
to the action of liquefied petroleum gases. The gas lines must be 
checked for leaks by the installer. This should be done with a soap 
solution watching for bubbles on all exposed connections, and if 
unexposed, a pressure test should be made.
Never use an exposed flame to check for leaks. Appliance must 
be disconnected from piping at inlet of control valve and pipe 
capped or plugged for pressure test. Never pressure test with 
appliance connected; control valve will sustain damage!
A gas valve and ground joint union should be installed in the gas 
line upstream of the gas control to aid in servicing. It is required by 
the National Fuel Gas Code that a drip line be installed near the gas 
inlet. This should consist of a vertical length of pipe tee connected 
into the gas line that is capped on the bottom in which condensation 
and foreign particles may collect.
Figure 2
Method of Installing a Tee Fitting Sediment Trap
Pressure Testing of the Gas Supply System
1. To check the inlet pressure to the gas valve, a 1/8” (3mm) N.P.T. 
plugged tapping, accessible for test gauge connection, must be 
placed immediately upstream of the gas supply connection to 
the appliance.
2. The appliance and its individual shutoff valve must be discon-
nected from the gas supply piping system during any pressure 
testing of that system at test pressures in excess of 1/2 psig 
(3.5 kPa)
3. The appliance must be isolated from the gas supply piping 
system by closing its individual manual shutoff valve during 
any pressure testing of the gas supply piping system at test 
pressures equal to or less than 1/2 psig (3.5 (kPa).
Attention! If one of the above procedures results in pressures in 
excess of 1/2 psig (14” w.c.) (3.5 kPa) on the appliance gas valve, 
it will result in a hazardous condition.
Checking Manifold Pressure
Both  Propane  and  Natural  gas  valves  have  a  built-in  pressure 
regulator in the gas valve. Natural gas models will have a manifold 
pressure of approximately 4.0” w.c. (.996kPa) at the valve outlet 
with the inlet pressure to the valve from a minimum of 5.0” w.c. 
(1.245kPa) for the purpose of input adjustment to a maximum of 
10.5” w.c. (2.61kPa). Propane gas models will have a manifold 
pressure  approximately  10.0”  w.c.  (2.49kPa)  at  the  valve  outlet 
with the inlet pressure to the valve from a minimum of 11.0” w.c. 
(2.739kPa) for the purpose of input adjustment to a maximum of 
13.0” w.c. (3.23kPa).
A 1/8” (3mm) N.P.T. plugged tapping, accessible for test gauge 
connection, is located on the outlet side of the gas control.