Goodman Mfg SS-CPC90-150 Benutzerhandbuch

Seite von 36
p
rodUCt
 s
peCifiCations
p
rodUCt
 s
peCifiCations
6 www.goodmanmfg.com 
SS-CPC90-150
p
rodUCt
 s
peCifiCations
 — 12½ t
ons
CPC150XXX
3BXXX
CPC150XXX
4BXXX
CPC150XXX
7BXXX
Cooling Capacity
Total, BTU/h
146,000
146,000
146,000
Sensible BTU/h
102,200
102,200
102,200
EER / IPLV
11.0 / 11.2
11.0 / 11.2
11.0 / 11.2
Decibels
83
83
83
ARI Reference #s
3542680
3542680
3542680
Evapoartor Motor / Coil
Motor Type
Belt Drive
Belt Drive
Belt Drive
Indoor Nominal CFM
5,000
5,000
5,000
Indoor Motor FLA (Cooling)
9.4
4.7
4.2
Horsepower - RPM
3.0 - 1,725
3.0 - 1,725
3.0 - 1,725
Piston Size (Cooling)
0.096
0.096
0.096
Filter Size
(4) 20" x 25" x 2"
(4) 20" x 25" x 2"
(4) 20" x 25" x 2"
Drain Size (NPT)
¾"
¾"
¾"
R-410A Refrigerant Charge  Cir #1 & #2
285 oz.
285 oz.
285 oz.
Evaporator Coil Face Area (ft
2
)
14.7
14.7
14.7
Rows Deep / Fins per Inch
4 / 15
4 / 15
4 / 15
Condenser Fan / Coil
Quantity of condenser Fan Motors
2
2
2
Horsepower - RPM
⅓ - 1,075
⅓ - 1,075
⅓ - 1,075
Fan Diameter / # Fan Blades
22/3
22/3
22/3
Outdoor Nominal CFM
7,200
7,200
7,200
Face Area (ft
2
)
35.3
35.3
35.3
Rows Deep / Fins per Inch
2/3 rows 15 fpi
2/3 rows 15 fpi
2/3 rows 15 fpi
Belt Drive Evap Fan Data
# of Wheels (D x W)
(1) 15" x 15"
(1) 15" x 15"
(1) 15" x 15"
Motor Sheave / Blower Sheave
VL40 / AK66
VL40 / AK66
VL40 / AK66
Belt
AX49
AX49
AX49
Compressor
Quantity / Type
1 / Scroll
1 / Scroll
1 / Scroll
Stage
Single
Single
Single
Compressor RLA / LRA ea.
22.4 / 149
10.6 / 75
7.7 / 54
Electrical Data / Static
Voltage / Phase / Frequency
208-230/3/60
460/3/60
575/3/60
Outdoor Fan FLA ea.
2.4
1.2
0.9
Total Unit Amps
59
28
21.4
Min. Circuit Ampacity
1
65
31
23
Max. Overcurrent Protection (amps)
2
80
40
30
Entrance Power Supply
Locating
Dimple
Locating
Dimple
Locating
Dimple
Entrance Control Voltage
Operating Weight (lbs)
1275
1275
1275
Ship Weight (lbs)
1300
1300
1300
¹   Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.
²   May use fuses or HACR-type circuit breakers of the same size as noted.
Note: Always check the S&R plate for electrical data on the unit being installed.