Goodman Mfg SS-CPC90-150 Benutzerhandbuch

Seite von 36
p
rodUCt
 s
peCifiCations
p
rodUCt
 s
peCifiCations
SS-CPC90-150
  
www.goodmanmfg.com 
5
p
rodUCt
 s
peCifiCations
 — 10 t
ons
CPC120 
XXX3BXXX
CPC120 
XXX4BXXX
CPC120 
XXX7BXXX
Cooling Capacity
Total BTU/h
118,000
118,000
118,000
Sensible BTU/h
87,300
87,300
87,300
EER / IEER
11.5 / 11.2
11.5 / 11.2
11.5 / 11.2
Decibels
83.0
83.0
83.0
ARI Reference #s
3023833
3023833
3023833
Evaporator Motor / Coil
Motor Type
Belt Drive
Belt Drive
Belt Drive
Indoor Nominal CFM
4,000
4,000
4,000
Indoor motor FLA (Cooling)
7.8
3.9
2.7
Horsepower - RPM
2.0/1725
2.0/1725
2.0/1725
Piston Size (Cooling)
0.086
0.086
0.086
Filter Size (Qty)
(4) 16” x 24” x 2”
(4) 16” x 24” x 2”
(4) 16” x 24” x 2”
Drain Size (NPT)
¾”
¾”
¾”
R-410A Refrigerant Charge  Cir #1 & #2
220 oz.
220 oz.
220 oz.
Evaporator Coil Face Area (ft²)
10.2
10.2
10.2
Rows Deep / Fins per Inch
4 / 14
4 / 14
4 / 14
Belt Drive Evap Fan Data
# of Wheels (D x W)
(1) 15” x 15”
(1) 15” x 15”
(1) 15” x 15”
Motor Sheave / Blower Sheave
VL40 / AK74
VL40 / AK74
VL40 / AK74
Belt 
AX51
AX51
AX51
Condenser Fan / Coil
Quantity of Condenser Fan Motors
2
2
2
Horsepower - RPM
⅓  - 1,075
⅓  - 1,075
⅓  - 1,075
Fan Diameter / # Fan Blades
22 / 3
22 / 3
22 / 3
Outdoor Nominal CFM
7,200
7,200
7,200
Face Area (ft²)
32.4
32.4
32.4
Rows Deep - Fins per Inch
2/2 rows - 22 fpi
2/2 rows - 22 fpi
2/2 rows - 22 fpi
Compressor
Quantity / Type
2 / Scroll
2 / Scroll
2 / Scroll
Stage
1
1
1
Electrical Data
Voltage/Phase/ Frequency
208-230/3/60
460/3/60
575/3/60
Quantity of Compressors 
2
2
2
Compressor RLA / LRA  ea.
16/110.0
7.8/52.0
5.7/38.9
Standard Max Static
2.0”
2.0”
2.0”
Outdoor Fan RLA  ea.
2.40
1.20
0.89
Total Unit Amps
45
22
16
Min. Circuit Ampacity¹
49
24
17
Max. Overcurrent Protection (amps)²
60.0
30
20
Entrance Power Supply
Locating
Dimple
Locating
Dimple
Locating
Dimple
Entrance Control Voltage
Operating Weight (lbs)
1135
1135
1135
Ship Weight (lbs)
1175
1175
1175
¹   Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.
²   May use fuses or HACR-type circuit breakers of the same size as noted.
Note: Always check the S&R plate for electrical data on the unit being installed.