Goodman Mfg SS-CPC90-150 Benutzerhandbuch

Seite von 36
p
rodUCt
 s
peCifiCations
p
rodUCt
 s
peCifiCations
4 www.goodmanmfg.com 
SS-CPC90-150
p
rodUCt
 s
peCifiCations
 — 8½ t
ons
CPC102
XXX3BXXX
CPC102
XXX4BXXX
CPC102
XXX7BXXX
Cooling Capacity
Total, BTU/h
102,000
102,000
102,000
Sensible BTU/h
70,380
70,380
70,380
EER / IEER
11.3 / 11.2
11.3 / 11.2
11.3 / 11.2
Decibels
83
83
83
ARI Reference #s
3620220
3620220
3620220
Evapoartor Motor / Coil
Motor Type
Belt Drive
Belt Drive
Belt Drive
Indoor Nominal CFM
3,400
3,400
3,400
Indoor Motor FLA (Cooling)
7.8
3.9
2.3
Horsepower - RPM
1725
1725
1725
Piston Size (Cooling)
0.08
0.08
0.08
Filter Size (Qty)
(4) 16” x 20” x 2”
(4) 16” x 20” x 2”
(4) 16” x 20” x 2”
Drain Size (NPT)
3/4"
3/4"
3/4"
R-410A Refrigerant Charge  Cir #1 & #2
180 oz.
180 oz.
180 oz.
Evaporator Coil Face Area (ft2)
8.9
8.9
8.9
Rows Deep / Fins per Inch
4 / 16
4 / 16
4 / 16
Belt Drive Evap Fan Data
# of Wheels (D x W)
1 (15" x 12")
1 (15" x 12")
1 (15" x 12")
Motor Sheave / Blower Sheave
VL40 / AK74
VL40 / AK74
VL40 / AK74
Belt
AX51
AX51
AX51
Condenser Fan / Coil
Quantity of Condenser Fan Motors
2
2
2
Horsepower - RPM
1/4" - 1,090
1/4" - 890
1/4" - 1,075
Fan Diameter / # Fan Blades
22 / 4
22 / 4
22 / 4
Outdoor Nominal CFM
7,600
7,600
7,600
Face Area (ft2)
13.25
13.25
13.25
Rows Deep / Fins per Inch
2 / 22
2 / 22
2 / 22
Compressor
Quantity / Type
2 / Scroll
2 / Scroll
2 / Scroll
Stage
1
1
1
Electrical Data / Static
Voltage / Phase / Frequency
230 / 3 / 60
460 / 3 / 60
575 / 3 / 60
Quantity of Compressors
2
2
2
Compressor RLA / LRA ea.
14.5 / 98
6.3 / 55
6.0 / 41
Standard Max Static
1"
1
1
Outdoor Fan FLA ea.
1.4
0.8
0.6
Total Unit Amps
39.6
18.1
15.5
Min. Circuit Ampacity¹
43.2
19.7
17
Max. Overcurrent Protection (amps)²
50
25
20
Entrance Power Supply
Locating
Dimple
Locating
Dimple
Locating
Dimple
Entrance Control Voltage
Operating Weight (lbs)
975
975
975
Ship Weight (lbs)
1000
1000
1000
¹   Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.
²   May use fuses or HACR-type circuit breakers of the same size as noted.
Note: Always check the S&R plate for electrical data on the unit being installed.