Enviro C-11212 Benutzerhandbuch

Seite von 35
Initial Installation
QUALIFIED INSTALLERS ONLY
G
AS
 L
INE
 C
ONNECTION
:
 
Warning: Only persons licensed to work with gas piping may make the necessary gas connections to 
this appliance.
Gas Line Connection: 
•This fireplace is equipped with a certified flexible pipe located on the right side of the unit, terminating 
in a 3⁄8” male NPT fitting. Consult the local authorities for local codes or use the CAN/CGA B149 (1 or 2) 
installation code in Canada. In the US, gas installations follow either local codes or the current edition of 
the National Fuel Gas Code ANSI Z223.1.
•The efficiency of this unit is a product thermal efficiency rating determined under continuous operating 
conditions and was determined independently of any installed system.
The  appliance  and  its  appliance  main  gas  valve 
must be disconnected from the gas supply piping 
system during any pressure testing of that system 
at test pressures in excess of 1⁄2 psi (3.5 kPa).  
The  appliance  must  be  isolated  from  the  gas 
supply  piping  system  by  closing  its  equipment 
shutoff  valve  during  any  pressure  testing  of  the 
gas supply piping system at test pressures equal 
to or less than 1⁄2 psi (3.5 kPa).
The  unit  must  be  isolated  from  the  gas  supply 
piping  system  by  closing  its  individual  manual 
shut off valve during any pressure testing of the 
gas supply piping system at pressures equal to 
or less than 1⁄2 psig (3.45 KPa).
O
L I
T
P
TP
TH
TP
TH
IN
OU
T
H
I
LO
N
OF
O
F
LI
P
T O
��������
�������� ���
�����
�������� ���
������
����
����� ����������
�����
��� �������
����
Main Burner
Natural Gas
Propane Gas
Orifice:
#32 DMS
#49 DMS
Venturi Setting:
1⁄2” Min.
7⁄8” Min.
Manifold Press:
3.8 W.C. (0.95 KPa) 11.0 W.C. (2.74 KPa)
Min. Manifold Press: 1.2 W.C. (0.30 KPa) 2.7 W.C. (0.67 KPa)
Max. Supply Press:
7.0 W.C. (1.74 KPa) 13.0 W.C. (3.28 KPa)
Min. Supply Press:
5.0 W.C. (1.24 KPa) 12.0 W.C. (2.98 KPa)
Max. Input:
41,000 BTU/hr 
(12.0 KW)
41,000 BTU/hr 
(12.0 KW)
Min. Input:
23,000 BTU/hr 
(6.7 KW)
21,000 BTU/hr 
(6.1 KW)
Always check for gas leaks with a soap 
and water solution after completing the 
required pressure test.
TO TEST VALVE PRESSURES:
The pressure taps are located on the top right 
of the valve (see Figure 24).
• Turn set screw one (1) turn counter-clockwise 
to loosen.
• Place 
5
/
16
  in  (8  mm)  I.D.  hose  over  the 
pressure taps.
• Check pressures using a manometer.
• When  finished,  release  pressure,  remove 
hose and tighten set screw.
NEVER USE AN OPEN FLAME FOR LEAK TESTING.
Figure 24: Fully labeled gas valve.
Table 5: Orifice and Pressure Information.
19