FAULT AND ALERT MESSAGES
Call the technical support phone number listed on the back cover for further technical assistance or to locate a qualified service technician 
in your area.
POSSIBLE CAUSES - CHECK/REPAIR
DISPLAYED FAULT/ALERT MESSAGE
•  The control system has failed to ignite the Main Burner.
•  Water heater is not properly grounded, loose or open ground wire 
to the Main Burner.
•  Dirty/corroded flame sensor, clean flame sensor with fine steel 
wool (replace if damaged).
•  Loose or open wiring to the flame sensor.
•  Loose or open wiring to the 24 V Gas Control Valve.
•  Supply gas turned off, low gas volume.
•  Intake air and/or vent piping is restricted or improperly installed.
•  Low or no manifold gas pressure to the Main Burner.
 
CHANGE
 
BACK 
ADVANCED
Ignition Failure
Fault occurred 2 mins ago
The water heater has failed to
ignite the burner.
Call a service professional:
Your Company Name Here
(press [DOWN] for more....)
•  The control system has detected the Blocked Exhaust Switch 
contacts are open.
•  The condensate drain is blocked filling the exhaust elbow with 
water - clear the condensate drain.
•  Loose or open wiring to the Blocked Exhaust Switch.
•  Restricted/blocked vent piping - condensate trapped in low point.
•  Excessive equivalent pipe length, exceeded the maximum number 
of 90° elbows or wrong pipe size used in the vent piping system.
•  Excessive wind outdoors pressurizing the vent system piping.
•  Excessive negative air pressure in the installed space.
 
CHANGE
 
BACK 
ADVANCED
Blocked Exhaust
Fault occurred 2 mins ago
The exhaust is blocked or
restricted. Ensure
condensate hose is draining.
Call a service professional:
Your Company Name Here
(press [DOWN] for more....)