FAULT AND ALERT MESSAGES (CONT)
Call the technical support phone number listed on the back cover for further technical assistance or to locate a qualified service technician 
in your area.
POSSIBLE CAUSES - CHECK/REPAIR
DISPLAYED FAULT/ALERT MESSAGE
•  The control system has detected the Blower Prover Switch 
contacts are closed when they should be open at the beginning of 
a heating cycle.
•  Pinched/shorted Blower Prover Switch wiring.
•  Jumper wire connected to the Blower Prover Switch - remove 
jumper wire. Jumper wires must never be used, read all Warnings.
•  Excessive wind outdoors pressurizing the vent system piping.
•  Excessive negative air pressure in the installed space.
 
CHANGE
 
BACK 
ADVANCED
Blower Prover Failure
Fault occurred 2 mins ago
The blower prover switch is
closed out of sequence.
Call a service professional:
Your Company Name Here
(press [DOWN] for more....)
•  The control system has detected the Blower Prover Switch 
contacts are remaining open after the control system has 
energized the Combustion Blower.
•  Loose or open wiring to the Blower Prover Switch.
•  Blower Prover Switch air sensing tube disconnected, kinked, filed 
with condensate, damaged or leaking - repair or replace tube.
•  Combustion Blower is not running when energized.
•  Loose or open wiring to Combustion Blower.
 
CHANGE
 
BACK 
ADVANCED
Blower Prover Open
Fault occurred 2 mins ago
The blower prover switch remains
open after the blower has been
energized.
Call a service professional:
Your Company Name Here
(press [DOWN] for more....)
•  The control system has detected the Blocked Intake Air Switch 
contacts are open.
•  Loose or open wiring to the Blocked Intake Air Switch.
•  Excessive equivalent pipe length, exceeded the maximum number 
of 90° elbows or wrong pipe size used in the intake air piping 
system.
•  Excessive negative air pressure in the installed space.
 
CHANGE
 
BACK 
ADVANCED
Blocked Air Intake
Fault occurred 2 mins ago
The combustion air intake is
restricted.
Call a service professional:
Your Company Name Here
(press [DOWN] for more....)
•  The control system has detected the ECO (energy cut out) Switch 
contacts are open.
•  The ECO switch is a normally closed switch that opens on a 
temperature rise to prevent excessive water temperature in the 
storage tank. The ECO switch is inside the Temperature Probe 
(two red wires).
•  Loose or open wiring to the ECO switch in the Temperature Probe 
- two red wires.
 
CHANGE
 
BACK 
ADVANCED
Energy Cut Out (ECO)
Fault occurred 2 mins ago
Tank temperature is excessive.
The water heater has been
disabled.
Call a service professional:
Your Company Name Here
(press [DOWN] for more....)
•  The control system has not detected any voltage from the powered 
anode rod.
•  No water in the storage tank.
•  Loose or open wiring connections to the powered anode rod.
•  Powered anode rod wiring shorted to ground.
•  The water heater is not properly grounded.
•  Loose or open ground wires.
•  Top fitting (3/4 inch bushing) of the powered anode rod was 
saturated with water during installation - with power to the 
water heater turned off, carefully remove anode rod and dry out 
bushing(s).
* Applies to models with powered anode option.
 
CHANGE
 
BACK 
ADVANCED
No Anode Voltage
Alert:
Alert occurred 2 mins ago
No voltage detected from
Powered Anode(s).
Call a service professional:
Your Company Name Here
(press [DOWN] for more....)