Installation Instructions
1.  Please fully read these instructions prior to installation and 
operation.
2.  Determine a suitable mounting location for the SL-2G 
control. The control must be placed in a location that is 
within 4’ of a 120VAC electrical outlet and within 8’ of the 
pipe being heated and controlled. 
3.  Mount the SL-2G to a rigid support such as a wall by way of 
the rear mounting slots.
4.  The SL-2G thermostat control is suitable for dry location  
(in-door) installations only. 
5.  Carefully uncoil and straighten the sensing wire/sensing bulb 
and attach it to the outer surface of the pipe being heated. 
The bulb on the end of the sensing wire must be located in 
an area that is experiencing the same freezing or damaging 
cold temperatures that the pipe is experiencing.  The sensing 
wire must not be kinked or compressed during installation. 
When used with the ILH product, the sensing wire must be 
secured to piping with tape, and not with devices such as 
cable ties or pipe clamps, as these will damage the sensing 
wire. The sensing wire must be protected from damage. 
Sensing wire damage will result in improper control of the 
heating cables and may result in frozen pipes and the risk of 
fire or electrical shock.
Operation Instructions
1.  The SL-2G thermostat control is designed to energize  
ILH heating cables when ambient temperatures drop  
below the set value. By controlling heating cable operation 
with the SL-2G, energy consumption is minimized.
2.  The bulb on the end of the sensing wire senses the 
temperature. If the temperature of the bulb drops below 
the pre-set temperature value the cable will energize, and 
remain energized until the sensing bulb senses temperatures 
above the pre-set value.
3.  The SL-2G can be tested for functionality by submerging the 
sensing bulb in ice water for 10 minutes; the GFCI receptacle 
will be energized.
4.  Disconnect the power to the SL-2G during the summer 
months.
5.  At the beginning of the heating season and monthly during 
operation, inspect the SL-2G control and its connection to 
the electrical power source. Similarly, check the GFCI on a 
monthly basis. Testing of the GFCI is dependent upon the 
temperature of the sensing bulb.
6.  Plug the SL-2G power cordset into a 120 VAC receptacle. 
The lighted plug on the cordset will illuminate indicating that 
there is power being supplied to the SL-2G control. Turn the 
SL-2G control knob to the maximum setting of 25°C (77°F). 
The GFCI receptacle indicator light should be off. If the GFCI 
receptacle indicator light is illuminated press the “Reset” 
button on the receptacle, the GFCI receptacle indicator 
light should then turn off. If the GFCI cannot be reset, then a 
fault exists. Do not attempt to bypass the GFCI. Bypassing the 
GFCI will result in the risk of fire or electrical shock.
7.  Set the desired protection temperature for your application 
by adjusting the control activation temperature between  
2° C and 25°C (36°F to 77°F).
8.  Plug in your ILH heating cable to the GFCI receptacle on the 
front of the SL-2G control.
      a)  If the ambient is below 21°C, turn the thermostat 
control knob to the maximum setting; the GFCI will be 
energized. Push the “TEST” button on the GFCI recptacle; a 
“click” should be heard and the receptacle indicator light 
will turn on. Push the “RESET” button on the GFCI recptacle 
to reset the power (the indicator light will turn off).
      b)  If the ambient temperature is above 22°C, you will need 
to “cool down” the sensing bulb to test the GFCI. It is 
recommended to wait until the bulb is below 21°C as 
in step a), however if this is not possible you will need to 
submerge the sensing bulb in ice water for 10 minutes and 
then follow the instructions as described in a) above. 
6.  The GFCI will not be affected by power interruptions.
7.  Discontinue use and remove any unit that has been 
damaged or has deteriorated for any reason. 
8.  Other conditions to look for are chewing by animals, water 
damage/corrosion or physical abuse.
Mounting
Slots
US  T. (800) 537-4732 / F. (888) 324-2440
CAN  T. (800) 794-3766 / F. (800) 361-4574
  
www.easyheat.com
 
2ºC/36ºF
9ºC/48ºF
17
ºC
/6
F
25ºC/77º
F
Power Cord to be hanked 
to maximum 4” dia
Neon Light
Clear Plug
Senseor Wire
Assembly
3-16 AWG Power Cord,  
4ft (from cabinet) CSA type SJT 105
°C