page 34 — dca220sscu/4i 60 hz generaTor • operaTion and parTs manual — rev. #0 (10/25/12) 
GeNeratOr start-Up prOCeDUre (aUtO MODe)
sTarTing (auTo mode)
  danger
Before connecting this generator to any 
building’s  electrical  system,  a 
licensed 
electrician  must  install  an  isolation 
(transfer)  switch.  Serious  damage  to 
the building’s electrical system may occur 
without this transfer switch.
  cauTion
When connecting the generator to a isolation (transfer) 
switch, 
alWaYs have power applied to the generator’s 
internal battery charger. This will ensure that the engine 
will not fail due to a dead battery.
  Warning
When  running  the  generator  in  the 
auTo  mode, 
remember the generator can start up at any time without 
warning. 
never attempt to perform any maintenance 
when the generator is in the auto mode.
  cauTion
The engine speed switch 
must be set to the “High” 
position when running in the 
auto-start mode. Failing 
to set the switch in the proper position can result in 
damage to your generator when it turns on.
NOTICE
When  the  generator  is  set  in  the 
auTo  mode,  the 
generator  will 
automatically  start  in  the  event  of 
commercial  power  falling  below  a  prescribed  level 
by  means  of  a  contact  closure  that  is  generated 
automatically by a transfer switch.
NOTICE
When  the 
Auto Off/Reset Manual switch is placed 
in the 
auTo position, the engine glow plugs will be 
warmed and the engine will start automatically.
When starting generator in 
auTo mode use the “Manual 
Start-up” procedure except where noted (see below).
1.  Perform steps 1 through 5 in the Before Starting section 
as outlined in the Manual Starting Procedure.
2.  Place the 
engine speed switch (Figure 49) in the 
high position  
Figure 49. Engine Speed Switch (High)
3.  Place the 
auto off/reset manual switch (Figure 50) 
in the 
auTo position.
Figure 50. 
auto off/reset manual
 Switch (AUTO)
4.  Continue operating the generator as outlined in the 
Manual Start-up procedure (start at step 5).