dca220sscu/4i 60 hz generaTor• operaTion manual — rev. #0 (10/25/12) — page 35
GeNeratOr shUt-DOWN prOCeDUres
normal shuTdoWn procedure
To shutdown the generator, use the following procedure:
1.  Place both the 
main, gFci and load circuit breakers 
as shown in Figure 51 to the 
oFF position.
Figure 51. Main, Aux. and GFCI  
Circuit Breakers (OFF)
2.  Place the 
engine speed switch (Figure 52) in the 
“LOW” (down) position.
Figure 52. Engine Speed Switch (Low)
3.  Let the engine cool by running it at low speed for 3-5 
minutes with no load applied.
4.  Place the 
auto off/reset manual switch (Figure 53) 
in the 
oFF/reseT position.
Figure 53. 
auto off/reset manual
 Switch
 (Off/Reset)
5.  Verify that all status LEDs on the ECU control panel 
are 
oFF (not lit). 
  Warning
never  stop  the  engine  suddenly  except  in  an 
emergency. 
6.  Remove all loads from the generator.
7.  Inspect entire generator for any damage or loosening of 
components that may have occurred during operation.
emergencY shuTdoWn procedure
1.  To stop the engine in the event of an emergency, 
push 
the emergency stop button (Figure 54) inward. This 
button is located on the engine operating panel, see 
Figure 5.
Figure 54. Emergency Stop Button
NOTICE
The emergency stop pushbutton switch is a push-lock 
type  switch. The  switch  contacts  will  remain  locked 
once the button has been pushed. To release the switch 
contacts rotate the button clockwise. The engine will not 
start unless the contacts are released.