How to reset the memory: 
1.  Set the MRES mode on the DIL switch (see the picture below). 
21







6FKDOWHUVWHOOXQJ 21  
6FKDOWHUVWHOOXQJ 2))  
 
Figure 4-33  Switch position MRES 
The STOP LED begins to flash.  
2.  Set DIL switch 1 to ON (STOP mode) after the STOP LED is lit in yellow color. 
3.  Return the DIL switch to MRES mode within three seconds. 
The memory is now being reset. 
4.  Wait for SIMOTION D410 to complete its restart. Set DIL switch 1, 2 and 3 to ON (RUN 
mode). 
The STOP LED lights after SIMOTION D410 has completed its memory reset. 
 
 
Note 
Memory reset is cancelled if you do not return the DIL switch to MRES as specified within 
three seconds. Repeat the procedure in this case. 
 
4.12.3 
Deleting user data from the CompactFlash Card 
Overview 
You can delete the user data using SIMOTION SCOUT. SIMOTION D410 must be operating 
in online mode. This deletes the following data: 
●  User data from the "volatile data" area 
●  Non-volatile data with the exception of IP and DP parameters 
●  User data on the CompactFlash Card (user folders), including the SINAMICS 
configuration data 
You can still go online to SIMOTION D410 at your programming device / PC. All licenses on 