Commissioning (software) 
 
4.13 System shutdown 
D410 
Commissioning Manual, 08/2008 Edition 
119
 
Restoring the default settings using the DIL switch 
1.  The power supply is shut down. 
2.  Set the MRES mode on the DIL switch of SIMOTION D410 (see the picture below). 
21







6FKDOWHUVWHOOXQJ 21  
6FKDOWHUVWHOOXQJ 2))  
 
Figure 4-34  Switch setting MRES 
3.  Restart the power supply. 
The buffered SRAM and user data are deleted. The default settings are loaded. 
SIMOTION D140 remains in STOP mode. 
4.  Change to the required mode by setting the DIL switch. 
 
 
 
Note 
The default communications parameters are now restored. You must re-configure the 
communication parameters of SIMOTION D410. 
4.13 
System shutdown 
All axes and system components must be in safe state before you shut down the system. 
You can set up this safe state by providing a separate motion task, for example.  
You can shut down the power supply after the system has reached a standstill state. 
 
 
Note 
You must observe the safety notices for SINAMICS components, which you can find in the 
corresponding SINAMICS manuals.