Siemens D410 Benutzerhandbuch

Seite von 150
 
Maintenance and service 
 
5.2 Replacing the fan 
D410 
Commissioning Manual, 08/2008 Edition 
125
 
5.2 
Replacing the fan 
Prerequisite 
Replace the fan if a fault message is output by the temperature monitoring function as a 
result of fan failure. The fan must be replaced if the fan is defective or the maximum 
operating hours counter is attained.  
The fan can be ordered as spare part, see "Spare parts and accessories" in the 
SIMOTION D410
 Manual. 
 
CAUTION 
 
The fan of the SIMOTION D410 module may only be replaced by qualified technical 
personnel and strictly in accordance with ESD guidelines! 
 
Replacing the fan 
How to replace the fan: 
1.  Unlock all snap-on hooks holding the plastic housing of the SIMOTION D410 using a flat-
blade screwdriver. 
2.  Remove the plastic enclosure. 
3.  You can now remove and replace the fan from the front without any additional tools. 
4.  Set the parameter of the p251 operating hours counter to "0". The parameter can only be 
changed in online mode. 
 
 
 
Note 
The parameter of the operating hours counter can only be set to "0". Any other values will 
be rejected. Restoring factory settings does not affect this parameter.