Maintenance and service 
 
5.1 Replacing modules 
 
D410 
124
 
Commissioning Manual, 08/2008 Edition 
5.1.2 
Replacing DRIVE-CLiQ components 
Replacing components 
DRIVE-CLiQ components support hot-plugging, that is, replacement or re-insertion while the 
system is in on or off state.  
Automatic upgrading/downgrading 
As of SINAMICS firmware version 2.5, the DRIVE-CLiQ components are automatically 
upgraded or downgraded to the version of the component firmware on the CF card. 
Components that cannot be upgrade or downgraded to the component firmware version on 
the CF card retain their firmware version. This is the case, for example, when a downgrade 
should be inhibited (e.g. "older firmware" is not supported by the "newer hardware"). The 
system ensures that the resulting combination possibilities of firmware versions are 
permitted. 
An upgrade/downgrade operation in progress is indicated on the components by a 0.5 Hz 
red-green flashing LED and on SIMOTION D410 by a 0.5 Hz yellow-flashing RDY LED. 
A successfully completed firmware upgrade/downgrade is indicated on the components by 
flashing at a frequency of 2 Hz and on the SIMOTION D410 by the yellow flashing of the 
RDY LED at 2 Hz. After the upgrade/downgrade is completed, the power must be cycled off 
and back on (POWER OFF/ON). The upgrade/downgrade function can be deactivated using 
the p7826 parameter in the expert list.  
 
Additional references 
Additional information is available in the 
SINAMICS S120
 Commissioning Manual.