Commissioning (software) 
 
4.3 Configuring the system in online mode 
D410 
Commissioning Manual, 08/2008 Edition 
73
 
4.3 
Configuring the system in online mode 
4.3.1 
Overview 
Introduction 
You can configure the plant in online mode after having completed its wiring. You can upload 
the data of SINAMICS components connected via DRIVE-CLiQ to your programming device 
/ PC using the "Automatic configuration" function. However, this functionality is only available 
within the initial commissioning phase. 
 
 
Note 
Components without DRIVE-CLiQ connection must be edited in offline mode. You may need 
to edit DRIVE-CLiQ components which were detected in the course of automatic 
configuration (for example, adding encoder data if using SMC modules). 
 
Prerequisites for online configuration 
●  You created a project in SIMOTION SCOUT and added a SIMOTION D410 to the project. 
●  You configured the communication between the the programming device / PC and 
SIMOTION D410. 
Procedure 
Steps involved in offline configuring: 
●  Establishing the online connection 
●  Starting automatic configuration 
●  Configuring SINAMICS components 
●  Aligning HW Config 
●  Downloading the project to SIMOTION D410